Functions
6-237
7SA6 Manual
C53000-G1176-C156-2
is switche
d
On
. With busbar side voltage transformers it can be switched
Off
. How-
ever, with a dead busbar the undervoltage protection picks up and expires, if it is not
blocked by other criteria via binary inputs.
6.16.3 Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
Addr.
Setting Title
Setting Options
Default Setting
Comments
3701
Uph-e>(>)
OFF
Alarm Only
ON
OFF
Operating mode Uph-e overvol-
tage prot.
3702
Uph-e>
1.0..170.0 V;
∞
85.0 V
Uph-e> Pickup
3703
T Uph-e>
0.00..30.00 sec;
∞
2.00 sec
T Uph-e> Time Delay
3704
Uph-e>>
1.0..170.0 V;
∞
100.0 V
Uph-e>> Pickup
3705
T Uph-e>>
0.00..30.00 sec;
∞
1.00 sec
T Uph-e>> Time Delay
3709A
Uph-e>(>) RESET
0.50..0.98
0.98
Uph-e>(>) Reset ratio
3711
Uph-ph>(>)
OFF
Alarm Only
ON
OFF
Operating mode Uph-ph over-
voltage prot.
3712
Uph-ph>
2.0..220.0 V;
∞
150.0 V
Uph-ph> Pickup
3713
T Uph-ph>
0.00..30.00 sec;
∞
2.00 sec
T Uph-ph> Time Delay
3714
Uph-ph>>
2.0..220.0 V;
∞
175.0 V
Uph-ph>> Pickup
3715
T Uph-ph>>
0.00..30.00 sec;
∞
1.00 sec
T Uph-ph>> Time Delay
3719A
Uphph>(>) RESET
0.50..0.98
0.98
Uph-ph>(>) Reset ratio
3721
3U0>(>) (or Ux)
OFF
Alarm Only
ON
OFF
Operating mode 3U0 (or Ux)
overvoltage
3722
3U0>
1.0..220.0 V;
∞
30.0 V
3U0> Pickup (or Ux>)
3723
T 3U0>
0.00..30.00 sec;
∞
2.00 sec
T 3U0> Time Delay (or T Ux>)
3724
3U0>>
1.0..220.0 V;
∞
50.0 V
3U0>> Pickup (or Ux>>)
3725
T 3U0>>
0.00..30.00 sec;
∞
1.00 sec
T 3U0>> Time Delay (or T Ux>>)
3729A
3U0>(>) RESET
0.50..0.98
0.95
3U0>(>) Reset ratio (or Ux)
3731
U1>(>)
OFF
Alarm Only
ON
OFF
Operating mode U1 overvoltage
prot.
3732
U1>
2.0..220.0 V;
∞
150.0 V
U1> Pickup
3733
T U1>
0.00..30.00 sec;
∞
2.00 sec
T U1> Time Delay
3734
U1>>
2.0..220.0 V;
∞
175.0 V
U1>> Pickup
3735
T U1>>
0.00..30.00 sec;
∞
1.00 sec
T U1>> Time Delay
3739A
U1>(>) RESET
0.50..0.98
0.98
U1>(>) Reset ratio
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...