Functions
6-25
7SA6 Manual
C53000-G1176-C156-2
Figure 6-14
Multiple fault on a double-circuit line next to a generato
r
Address
1156A
Trip2phFlt
determines that the short-circuit protection functions
perform only a single-pole trip in case of isolated two-phase faults (clear of ground),
provided that single-pole tripping is possible and permitted. This allows a single-pole
rapid automatic reclosure cycle for this kind of fault. The trip type can be set to
1pole
leading phase
or
1pole lagging phase
. The parameter is only available in ver-
sions with single-pole tripping. This setting can only be modified with DIGSI
®
4 under
“Additional Settings”. If this option is used, it must be born in mind that the phase
preference should be the same throughout the entire network and that it must be the
same at all ends of one line. More information on the function is also contained in Sec-
tion 6.22.3 Overall Fault Detection Logic of the Device. The default setting is
triple-
pole
.
6.1.3.1
Settings
Note: The indicated secondary current values and values of impedance for setting
ranges and default settings refer to I
N
= 1 A. For the nominal current 5 A the current
values are to be multiplied by 5. The values of impedance are divided by 5.
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
~
L1–E
L2–E
Addr.
Setting Title
Setting Options
Default Setting
Comments
1103
FullScaleVolt.
1.0..1200.0 kV; 0
400.0 kV
Measurement: Full Scale
Voltage (100%)
1104
FullScaleCurr.
10..5000 A
1000 A
Measurement: Full Scale Cur-
rent (100%)
1105
Line Angle
30..89
°
85
°
Line Angle
1110
x'
0.0050..6.5000 Ohm / km
0.1500 Ohm / km
x' - Line Reactance per length
unit
1111
Line Length
1.0..1000.0 km
100.0 km
Line Length
1112
x'
0.0050..10.0000 Ohm / mile
0.2420 Ohm / mile
x' - Line Reactance per length
unit
1113
Line Length
0.6..650.0 Miles
62.1 Miles
Line Length
1116
RE/RL(Z1)
-0.33..7.00
1.00
Zero seq. comp. factor RE/RL
for Z1
1117
XE/XL(Z1)
-0.33..7.00
1.00
Zero seq. comp. factor XE/XL for
Z1
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...