Technical Data
10-30
7SA6 Manual
C53000-G1176-C156
10.9
External Direct and Remote Tripping
External Trip of the
Local Breaker
Operating time, total
approx. 11 ms
Trip time delay
0.00 s to 30.00 s,
∞
(steps 0.01 s)
or
∞
(ineffective)
Time expiry tolerance
1 % of set value or 10 ms
The set time is a pure delay time.
10.10 Overcurrent Protection
Operating Modes
As emergency overcurrent protection or back-up overcurrent protection:
Emergency overcurrent protection
operates on failure of the measured
voltage,
– on trip of a voltage secondary miniature
circuit breaker (via binary input)
– on detection of a fuse failure in the
voltage secondary circuit
Back-up overcurrent protection
operates independent on any events
Characteristics
Definite time stages
(definite)
I
Ph
>>,3I
0
>>, I
Ph
>, 3I
0
>
Inverse time stage
(IDMT)
I
P
, 3I
0P
one of the characteristics according to
Figure 10-1 to 10-3 (see Section 10.5)
can be selected
High Set Stages
Pickup values
I
Ph
>> (phases) 0.10 A to 25.00 A
1
)
(steps 0.01 A)
or
∞
(ineffective)
3I
0
>> (earth)
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
∞
(ineffective)
Time delays
T
IPh>
(phases) 0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
T
3I0>>
(earth)
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Drop-off to pick-up ratioapprox. 0.95 for I/I
N
≥
0.5
Pick-up time
approx. 25 ms
Drop-off time
approx. 30 ms
Tolerances
currents
3 % of set value or 1% nominal current
times
1 % of set value or 10 ms
The set times are pure delay times.
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied by 5.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...