– Test voltage
500 V; 50 Hz
– Transmission speed
up to 12 MBd
– Maximum transmission distance
1000 m at
≤
93.75 kBd
500 m at
≤
187.5 kBd
200 m at
≤
1.5 MBd
100 m at
≤
12 MBd
Optical fibre
– Connector Type
ST–connector
for flush mounted case
rear panel, mounting location “B”
for surface mounted case
at the inclined housing on the case bottom
– Optical wavelength
λ
= 820 nm
– Laser class 1 acc. EN 60825–1/ –2
using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
– Permissible optical signal attenuation max. 8 dB, using glass fibre 62.5/125 µm
– Maximum transmission distance
1.5 km (0.93 miles)
– Character idle state
selectable; factory setting: “Light off”
Profibus Optical
– Connector Type
ST–plug
single ring or twin ring depending on
ordered version
– Connection for flush mounted case
rear panel, mounting location “B”
for surface mounted case please use the relay with Profibus RS485
interface and separate fibre optic converter.
– Transmission speed
to 1.5 MBd
recommended:
> 500 kBd
– Optical wavelength
λ
= 820 nm
– Laser class 1 acc. EN 60825–1/ –2
using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
– Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 µm
– Maximum transmission distance
1500 m (4920 ft)
Time
Synchronization
Interface
– Signal type
DCF77/IRIG B-Signal
– Connection for flush mounted case
rear panel, mounting location “A”
9-pin DSUB socket
for surface mounted case
at the terminal on the case bottom
– Nominal signal voltages
optional 5 V, 12 V or 24 V
– Signal level and burden:
Nominal signal input voltage
5 V
12 V
24 V
U
IHigh
6.0 V
15.8 V
31 V
U
ILow
1.0 V for I
ILow
= 0.25 mA 1.4 V
for I
ILow
= 0.25 mA 1.9 V
for I
ILow
= 0.25 mA
I
IHigh
4.5 mA to 9.4 mA
4.5 mA to 9.3 mA
4.5 mA to 8.7 mA
R
I
890
Ω
for
U
I
= 4 V
640
Ω
for
U
I
= 6 V
1930
Ω
for
U
I
= 8.7 V
1700
Ω
for
U
I
= 15.8 V
3780
Ω
for
U
I
= 17 V
3560
Ω
for
U
I
= 31 V
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...