Appendix
B-19
7SA6 Manual
C53000-G1176-C156-2
3721
3U0>(>) (or Ux)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode 3U0 (or Ux) overvolt-
age
3722
3U0>
Voltage Protection
1.0..220.0 V;
∞
30.0 V
3U0> Pickup (or Ux>)
3723
T 3U0>
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T 3U0> Time Delay (or T Ux>)
3724
3U0>>
Voltage Protection
1.0..220.0 V;
∞
50.0 V
3U0>> Pickup (or Ux>>)
3725
T 3U0>>
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T 3U0>> Time Delay (or T Ux>>)
3729A
3U0>(>) RESET
Voltage Protection
0.50..0.98
0.95
3U0>(>) Reset ratio (or Ux)
3731
U1>(>)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode U1 overvoltage prot.
3732
U1>
Voltage Protection
2.0..220.0 V;
∞
150.0 V
U1> Pickup
3733
T U1>
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T U1> Time Delay
3734
U1>>
Voltage Protection
2.0..220.0 V;
∞
175.0 V
U1>> Pickup
3735
T U1>>
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T U1>> Time Delay
3739A
U1>(>) RESET
Voltage Protection
0.50..0.98
0.98
U1>(>) Reset ratio
3741
U2>(>)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode U2 overvoltage prot.
3742
U2>
Voltage Protection
2.0..220.0 V;
∞
30.0 V
U2> Pickup
3743
T U2>
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T U2> Time Delay
3744
U2>>
Voltage Protection
2.0..220.0 V;
∞
50.0 V
U2>> Pickup
3745
T U2>>
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T U2>> Time Delay
3749A
U2>(>) RESET
Voltage Protection
0.50..0.98
0.98
U2>(>) Reset ratio
3751
Uph-e<(<)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode Uph-e undervoltage
prot.
3752
Uph-e<
Voltage Protection
1.0..100.0 V; 0
30.0 V
Uph-e< Pickup
3753
T Uph-e<
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T Uph-e< Time Delay
3754
Uph-e<<
Voltage Protection
1.0..100.0 V; 0
10.0 V
Uph-e<< Pickup
3755
T Uph-e<<
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T Uph-e<< Time Delay
3758
CURR.SUP. Uphe< Voltage Protection
ON
OFF
ON
Current supervision (Uph-e)
3761
Uph-ph<(<)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode Uph-ph undervoltage
prot.
3762
Uph-ph<
Voltage Protection
1.0..175.0 V; 0
50.0 V
Uph-ph< Pickup
3763
T Uph-ph<
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T Uph-ph< Time Delay
3764
Uph-ph<<
Voltage Protection
1.0..175.0 V; 0
17.0 V
Uph-ph<< Pickup
3765
T Uphph<<
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T Uph-ph<< Time Delay
3768
CURR.SUP.Uphph
<
Voltage Protection
ON
OFF
ON
Current supervision (Uph-ph)
3771
U1<(<)
Voltage Protection
OFF
Alarm Only
ON
OFF
Operating mode U1 undervoltage prot.
3772
U1<
Voltage Protection
1.0..100.0 V; 0
30.0 V
U1< Pickup
3773
T U1<
Voltage Protection
0.00..30.00 sec;
∞
2.00 sec
T U1< Time Delay
3774
U1<<
Voltage Protection
1.0..100.0 V; 0
10.0 V
U1<< Pickup
3775
T U1<<
Voltage Protection
0.00..30.00 sec;
∞
1.00 sec
T U1<< Time Delay
3778
CURR.SUP.U1<
Voltage Protection
ON
OFF
ON
Current supervision (U1)
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...