Instruction sheet 

MTL surge protection

ZoneBarrier 4PPOE range

 

Din rail mount protection system

Eaton Electric Limited, 
Great Marlings, Butterfield, Luton
Beds, LU2 8DL, UK.
Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283
E-mail: [email protected]
www.eaton.com
© 2023 Eaton 
All Rights Reserved
Publication No. INS 801-774 Rev A 170323
June 2023

1

CAUTION

IMPORTANT SAFETY INSTRUCTIONS

1. Never install ethernet wiring during a          

lightning storm.
2. This product is intended for INDOOR USE                     

ONLY.
3.  Secondary  Protectors  are  intended  for  use  on  the          

equipment side of a listed UL 497B Protector.
4. Risk of Electric Shock - Protector is not to be used 

without the arrestor assembly installed.

Installation

1.  Read and understand all instructions.

2.  The SPD modules can be installed individually, 

mounting to any flat surface using the two screw holes. 

SPD modules can also be installed on a Din Rail.

In planning an installation, location of the SPD unit in 

close proximity to the correct ground point is essential 

for protection performance. The correct ground point is 

defined as the ground reference used by the system to be 

protected. In most applications this is AC power ground. 

MINIMIZE the distance between the SPD unit and the 

identified ground point as short as possible.

Stand-alone installation

3.  To install the SPD unit as a stand-alone unit, attach a 

ground wire (minimum #16AWG for Secondary Protector) 

to the SPD using the recommended accessories and using 

screws(or bolts) as appropriate, mount the unit to the flat 

surface (see figure 1).

           

   

Figure 1 - Stand-alone Installation

Mounting and grounding on a Din Rail

4.  To install a SPD surge protector on a Din Rail, locate the 

Din Rail foot over the Din Rail and securely push the  clip 

onto the Din Rail. Rotate downward and push the SPD onto 

the Din Rail until the latch snaps on to the rail. (see figure 2).

   

            Figure 2 - Mounting and grounding on a Din Rail

The surge protector is now securely grounded to the Din 

Rail. An existing or customer supplied Din Rail can be 

used providing the rail is securely connected to the correct 

ground (see grounding section). To remove a module, 

gently pull the release latch forward and rotate the SPD 

upward off of the Din Rail..

5.  Connect the incoming line to the port marked 

“unprotected” on the SPD  module. Run cable from the 

SPD port marked “protected” to the equipment to be 

protected. Patch cable wire size must not exceed #24AWG.

6.  Connect a green ground wire from the Din Rail or 

from the SPD unit to the identified grounding point (see 

grounding section). 

7.  Save these instructions.

Grounding

The Din Rail grounding stud must be connected to the 

ground reference used by the system being protected. In a 

computer room environment this grounding point may be 

the ground bar in the AC power panel. Ground leads longer 

than 0.25 meter are not recommended

 

   