Functions
6-52
7SA6 Manual
C53000-G1176-C156-2
6.2.3.4
Information Overview
1242
ϕ
load (Ø-E)
20..60
°
45
°
PHI load, maximum Load
Angle (ph-e)
1243
R load (Ø-Ø)
0.100..250.000 Ohm;
∞
∞
Ohm
R load, minimum Load Impe-
dance (ph-ph)
1244
ϕ
load (Ø-Ø)
20..60
°
45
°
PHI load, maximum Load
Angle (ph-ph)
1203
3I0> Threshold
0.05..4.00 A
0.10 A
3I0 threshold for neutral cur-
rent pickup
1204
3U0> Threshold
1..100 V;
∞
5 V
3U0 threshold zero seq.
voltage pickup
1205
3U0> COMP/
ISOL.
10..200 V
40 V
3U0> pickup (comp/ isol. star-
point)
1206
T3I0 1PHAS
0.00..0.50 sec;
∞
0.04 sec
Delay 1ph-faults (comp/isol.
star-point)
1207A
3I0>/ Iphmax
0.05..0.30
0.10
3I0>-pickup-stabilisation (3I0>
/Iphmax)
1220
PHASE
PREF.2phe
L3 (L1) acyclic
L1 (L3) acyclic
L2 (L1) acyclic
L1 (L2) acyclic
L3 (L2) acyclic
L2 (L3) acyclic
L3 (L1) cyclic
L1 (L3) cyclic
all loops
L3 (L1) acyclic
Phase preference for 2ph-e
faults
1221A
2Ph-E faults
block leading ph-e loop
block lagging ph-e loop
all loops
only phase-phase loops
only phase-earth loops
block leading ph-e
loop
Loop selection with 2Ph-E
faults
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
3603
>BLOCK Distance
>BLOCK Distance protection
3611
>ENABLE Z1B
>ENABLE Z1B (with setted Time Delay)
3613
>ENABLE Z1Binst
>ENABLE Z1B instantanous (w/o T-Delay)
3617
>BLOCK Z4-Trip
>BLOCK Z4-Trip
3618
>BLOCK Z5-Trip
>BLOCK Z5-Trip
3651
Dist. OFF
Distance is switched off
3652
Dist. BLOCK
Distance is BLOCKED
3653
Dist. ACTIVE
Distance is ACTIVE
3654
Dis.ErrorK0(Z1)
Setting error K0(Z1) or Angle K0(Z1)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...