Technical Data
10-45
7SA6 Manual
C53000-G1176-C156
Thermal measured values
Θ
L1
/
Θ
TRIP
;
Θ
L2
/
Θ
TRIP
;
Θ
L3
/
Θ
TRIP
;
Θ
/
Θ
TRIP
related to tripping temperature rise
Operational measured values
of synchro check
U
line
; U
sync
; U
diff
in kV primary
f
line
; f
sync
; f
diff
in Hz;
ϕ
diff
in °
Measured values of earth fault
I
Ea
; I
Er
(active and reactive component
detection in non-earthed systems
of earth fault current (residual current)
in A primary and mA secondary
Long–term mean value
I
L1
dmd; I
L2
dmd; I
L3
dmd; I
1
dmd;
Pdmd; Pdmd Forw, Pdmd Rev;
Qdmd; QdmdForw; QdmdRev;
Sdmd
in primary values
Minimum and maximum values
I
L1
; I
L2
; I
L3
; I
1
; I
L1
d; I
L2
d; I
L3
d; I
1
d;
U
L1–E
; U
L2–E
; U
L3–E
; U
1
;
U
L1–L2
; U
L2–L3
; U
L3–L1
;3U
0
;
PForw; PRev; QForw; QRev; S;
Pd; Qd; Sd;
cos
ϕ
Pos; cos
ϕ
Neg; f
in primary values
Remote measured values
for currents
I
L1
; I
L2
; I
L3
of remote end
ϕ
(I
L1
);
ϕ
(I
L2
);
ϕ
(I
L3
) (remote
versus local) in °
Remote measured values
for voltages
U
L1
; U
L2
; U
L3
of remote end
ϕ
(U
L1
);
ϕ
(U
L2
);
ϕ
(U
L3
) (remote
versus local) in°
Analog Outputs
(optional)
Quantity
max. 4 (dependent on order variant)
Possible measured values
I
L2
; U
L2–L3
; |P|; |Q| in %
Possible fault values
fault distance d in % or km/miles;
latest max. fault current
Range
0 mA to 22.5 mA
Output time for fault values
0.10 s to 180.00 s;
∞
(steps 0.01 s)
Operation Event
Log Buffer
Capacity
200 records
Earth Fault
Detection Buffer
(Non-earthed
Systems)
Capacity
8 earth faults with a total sum of max.
200 records
Fault Protocol
(Trip Log Buffer)
Capacity
8 faults with a total sum of max.
600 records
Fault Recording
Number of stored fault records
max. 8
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...