Configuration
5-6
7SA6 Manual
C53000-G1176-C156-2
According to the order variant the device is provided with analog outputs (0 to 20 mA).
2 outputs can be located on Port B (Mounting location “B”), another 2 on Port D
(mounting location “D”). In address
150
to
153
the user can select which analog val-
ues shall be output. Some measured values and the location of the fault are also avail-
able.
5.1.1
Settings
Addr.
Setting Title
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
110
Trip mode
3pole only
1-/3pole
3pole only
Trip mode
114
Dis. PICKUP
Z< (quadrilateral)
I> (overcurrent)
U/I (voltage controlled over-
current)
U/I/phi (voltage & angle con-
trolled o/c)
Disabled
Z< (quadrilateral)
Distance protection pickup pro-
gram
120
Power Swing
Disabled
Enabled
Disabled
Power Swing detection
121
Teleprot. Dist.
PUTT (Z1B acceleration)
PUTT (acceleration with Pik-
kup)
POTT
Directional Comparison Pik-
kup
Unblocking
Blocking
Reverse Interlocking
Pilot wire comparison
POTT over Protection Inter-
face
Disabled
Disabled
Teleprotection for Distance prot.
122
DTT Direct Trip
Disabled
Enabled
Disabled
DTT Direct Transfer Trip
124
SOTF Overcurr.
Disabled
Enabled
Disabled
Instantaneous HighSpeed SOTF
Overcurrent
125
Weak Infeed
Disabled
Enabled
Disabled
Weak Infeed (Trip and/or Echo)
126
Back-Up O/C
Disabled
Time Overcurrent Curve IEC
Time Overcurrent Curve
ANSI
Time Overcurrent
Curve IEC
Backup overcurrent
130
Sens. Earth Flt
Disabled
Enabled
Disabled
Sensitive Earth Flt.(comp/ isol.
starp.)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...