Technical Data
10-28
7SA6 Manual
C53000-G1176-C156
10.7
Weak-Infeed Tripping
Operation method
Phase segregated undervoltage detection after reception of a carrier signal from the
remote end
Undervoltage
Detection
Setting value
U
PhE
<
2 V to 70 V
(steps 1 V)
Drop-off to pick-up ratio
approx. 1.05
Pick-up tolerances
≤
5 % of set value or 0.5 V
Times
Release delay
0.00 s to 30.00 s
(steps 0.01 s)
Release prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms