Functions
6-151
7SA6 Manual
C53000-G1176-C156-2
6.8.2
Applying the Function Parameter Settings
General
The teleprotection supplement for earth fault protection is only operational if it was set
to one of the available modes during the configuration of the device (address
132
).
Depending on this configuration, only those parameters which are applicable to the
selected mode appear here. If the teleprotection supplement is not required the ad-
dress
132
is set to
Teleprot. E/F
=
Disabled
.
Conventional
Transmission
The following modes are possible with conventional transmission links:
−
Dir.Comp.Pickup
=Directional Comparison Scheme, as described in Sub-sec-
tion 6.8.1.1,
−
Unblocking
= Directional Unblocking Scheme, as described in Sub-section
6.8.1.2,
−
Blocking
= Directional Blocking Scheme, as described in Sub-section
6.8.1.3.
In address
3201
FCT Telep. E/F
the application of teleprotection can be switched
ON
or
OFF
.
If the teleprotection has to be applied to a three terminal line the setting in address
3202
must be
Line Config.
=
Three terminals
, if not, the setting remains
Two
terminals
.
Digital
Transmission
The following mode is possible with digital transmission using the protection data
interface:
−
Dir.Comp.Pickup
Directional Comparison Scheme, as described in Section
6.8.1.1.
The desired mode is selected at address
3201
FCT Telep. E/F
. Here, the use of
a signal transmission mode can also be switched
ON
or
OFF
. The address
3202
Line
Config.
is not relevant in that case. The earth fault directional comparison pickup
scheme is only effective if the parameter
132
Teleprot. E/F
has been set to
Directional Comparison over Protection Interface
in all devices of the
setup.
Earth Fault
Protection
Prerequisites
In the application of the comparison schemes, absolute care must be taken that both
line ends recognize an external earth fault (earth fault through-current) in order to
avoid a faulty echo signal in the case of the permissive schemes, or in order to ensure
the blocking signal in the case of the blocking scheme. If, during an earth fault accord-
ing to Figure 6-87, the protection at B does not recognize the fault, this would be inter-
preted as a fault with single sided infeed from A (echo from B or no blocking signal
from B), which would lead to unwanted tripping by the protection at A. For this reason,
the earth fault protection has an earth current stage
3IoMin Teleprot
(address
3105
). This stage must be set more sensitive than the earth current stage used for the
teleprotection. The larger the capacitive earth current (
I
EC
in Figure 6-87) is the small-
er this stage must be set. On overhead lines a setting equal to 70 % to 80 % of the
earth current stage is usually adequate. On cables or very long lines where the capac-
itive currents in the event of an earth fault are of the same order of magnitude as the
earth fault currents the echo function should not be used or restricted to the case
where the circuit breaker is open; the blocking scheme should not be used under these
conditions at all. This setting can only be modified with DIGSI
®
4 under “Additional
Settings
”.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...