Technical Data
10-18
7SA6 Manual
C53000-G1176-C156
10.3
Power Swing Supplement (optional)
Power swing detection
Rate of change of the impedance phasor
and observation of the path curve
Max. power swing frequency
approx. 7 Hz
Power swing blocking programs
Block 1st zone only
Block higher zones
Block 1st and 2nd zone
Block all zones
Out-of-step trip
Trip following instable power swings
(out-of-step)
10.4
Distance Protection Teleprotection Schemes
Mode
For two line ends
with one channel for each direction or
with three channels for each direction
(for phase segregated transmission)
For three line ends
with one channel for each direction and
opposite line end
Underreach
Schemes
Method
Permissive Underreach Transfer Trip
(PUTT) (with overreaching zone Z1B)
PUTT (Pickup)
Direct transfer trip
Send signal prolongation
0.00 s to 30.00 s
(steps 0.00 s)
Underreach
Schemes via
Protection Data
Interface
(optional)
Method
Permissive Underreach Transfer Trip
(PUTT) (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 (steps 0.01 s)
Overreach
schemes
Methods
Permissive Overreach Transfer Trip
(POTT) (with overreaching zone Z1B)
Dir. Comp. Pickup
Unblocking (with overreaching zone Z1B)
Blocking (with overreaching zone Z1B)
Pilot wire comp.
Rev. Interlock
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...