Appendix
B-6
7SA6 Manual
C53000-G1176-C156-2
1140A
I-CTsat. Thres.
Power System Data
2
0.2..50.0 A;
∞
20.0 A
CT Saturation Threshold
1150A
SI Time Man.Cl
Power System Data
2
0.01..30.00 sec
0.30 sec
Seal-in Time after MANUAL closures
1151
MAN. CLOSE
Power System Data
2
with Synchronism-check
without Synchronism-check
NO
without Synchronism-check
Manual CLOSE COMMAND genera-
tion
1155
3pole coupling
Power System Data
2
with Pickup
with Trip
with Trip
3 pole coupling
1156A
Trip2phFlt
Power System Data
2
3pole
1pole, leading phase
1pole, lagging phase
3pole
Trip type with 2phase faults
1201
FCT Distance
Distance protec-
tion, general set-
tings
ON
OFF
ON
Distance protection is
1202
Minimum Iph>
Distance protec-
tion, general set-
tings
0.10..4.00 A
0.10 A
Phase Current threshold for dist.
meas.
1203
3I0> Threshold
Distance protec-
tion, general set-
tings
0.05..4.00 A
0.10 A
3I0 threshold for neutral current pickup
1204
3U0> Threshold
Distance protec-
tion, general set-
tings
1..100 V;
∞
5 V
3U0 threshold zero seq. voltage pickup
1205
3U0> COMP/ISOL.
Distance protec-
tion, general set-
tings
10..200 V
40 V
3U0> pickup (comp/ isol. star-point)
1206
T3I0 1PHAS
Distance protec-
tion, general set-
tings
0.00..0.50 sec;
∞
0.04 sec
Delay 1ph-faults (comp/isol. star-point)
1207A
3I0>/ Iphmax
Distance protec-
tion, general set-
tings
0.05..0.30
0.10
3I0>-pickup-stabilisation (3I0> /Iph-
max)
1215
Paral.Line Comp
Distance protec-
tion, general set-
tings
NO
YES
YES
Mutual coupling parall.line compensa-
tion
1220
PHASE PREF.2phe Distance protec-
tion, general set-
tings
L3 (L1) acyclic
L1 (L3) acyclic
L2 (L1) acyclic
L1 (L2) acyclic
L3 (L2) acyclic
L2 (L3) acyclic
L3 (L1) cyclic
L1 (L3) cyclic
all loops
L3 (L1) acyclic
Phase preference for 2ph-e faults
1221A
2Ph-E faults
Distance protec-
tion, general set-
tings
block leading ph-e loop
block lagging ph-e loop
all loops
only phase-phase loops
only phase-earth loops
block leading ph-e loop
Loop selection with 2Ph-E faults
1232
SOTF zone
Distance protec-
tion, general set-
tings
with Pickup (non-directional)
with Zone Z1B
Inactive
Inactive
Instantaneous trip after SwitchOnTo-
Fault
1241
R load (Ø-E)
Distance protec-
tion, general set-
tings
0.100..250.000 Ohm;
∞
∞
Ohm
R load, minimum Load Impedance (ph-
e)
1242
ϕ
load (Ø-E)
Distance protec-
tion, general set-
tings
20..60
°
45
°
PHI load, maximum Load Angle (ph-e)
1243
R load (Ø-Ø)
Distance protec-
tion, general set-
tings
0.100..250.000 Ohm;
∞
∞
Ohm
R load, minimum Load Impedance (ph-
ph)
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...