Technical Data
10-19
7SA6 Manual
C53000-G1176-C156
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo impulse duration
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times.
Overreach
Schemes via
Protection Data
Interface
(optional)
Methods
Directional comparison pickup scheme
Permissive Overreach Transfer Trip
(POTT) (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 s(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo pulse duration
0.00 s to30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times
10.5
Earth Fault Protection in Earthed Systems (optional)
Characteristics
Definite time stages
(definite)
3I
0
>>>,3I
0
>>,3I
0
>
Inverse time stage
(IDMT)
3I
0P
one of the characteristics according to
Figure 10-1 to 10-12 can be selected
Voltage-dependent stage (U
0
inverse)
characteristic according to 10-8
Very High Set Stage
Pickup value
3I
0
>>>
0.50 A to 25.00 A
1
)
(steps 0.01 A)
T
3I0>>>
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Drop-off to pick-up ratio
approx. 0.95 for I/I
N
≥
0.5
Pickup time
approx. 35 ms
Drop-off time
approx. 30 ms
Tolerances
current
3 % of set value or 1% nominal current
time
1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
High Set Stage
Pickup value
3I
0
>>
0.20 A to 25.00 A
1
)
(steps 0.01 A)
Delay time
T
3I0>>
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Drop-off to pick-up ratio
approx. 0.95 for I/I
N
≥
0.5
Pickup time
approx. 35 ms
Drop-off time
approx. 30 ms
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...