Appendix
B-5
7SA6 Manual
C53000-G1176-C156-2
610
FltDisp.LED/LCD
Device
Display Targets on every
Pickup
Display Targets on TRIP
only
Display Targets on every
Pickup
Fault Display on LED / LCD
615
Spont. FltDisp.
Device
NO
YES
NO
Spontaneous display of flt.annuncia-
tions
1103
FullScaleVolt.
Power System Data
2
1.0..1200.0 kV; 0
400.0 kV
Measurement: Full Scale Voltage
(100%)
1104
FullScaleCurr.
Power System Data
2
10..5000 A
1000 A
Measurement: Full Scale Current
(100%)
1105
Line Angle
Power System Data
2
30..89
°
85
°
Line Angle
1110
x'
Power System Data
2
0.0050..6.5000 Ohm / km
0.1500 Ohm / km
x' - Line Reactance per length unit
1111
Line Length
Power System Data
2
1.0..1000.0 km
100.0 km
Line Length
1112
x'
Power System Data
2
0.0050..10.0000 Ohm / mile 0.2420 Ohm / mile
x' - Line Reactance per length unit
1113
Line Length
Power System Data
2
0.6..650.0 Miles
62.1 Miles
Line Length
1116
RE/RL(Z1)
Power System Data
2
-0.33..7.00
1.00
Zero seq. comp. factor RE/RL for Z1
1117
XE/XL(Z1)
Power System Data
2
-0.33..7.00
1.00
Zero seq. comp. factor XE/XL for Z1
1118
RE/RL(Z1B...Z5)
Power System Data
2
-0.33..7.00
1.00
Zero seq. comp.factor RE/RL for
Z1B...Z5
1119
XE/XL(Z1B...Z5)
Power System Data
2
-0.33..7.00
1.00
Zero seq. comp.factor XE/XL for
Z1B...Z5
1120
K0 (Z1)
Power System Data
2
0.000..4.000
1.000
Zero seq. comp. factor K0 for zone Z1
1121
Angle K0(Z1)
Power System Data
2
-135.00..135.00
°
0.00
°
Zero seq. comp. angle for zone Z1
1122
K0 (> Z1)
Power System Data
2
0.000..4.000
1.000
Zero seq.comp.factor K0,higher zones
>Z1
1123
AngleI K0(> Z1)
Power System Data
2
-135.00..135.00
°
0.00
°
Zero seq. comp. angle, higher zones
>Z1
1126
RM/RL ParalLine
Power System Data
2
0.00..8.00
0.00
Mutual Parallel Line comp. ratio RM/
RL
1127
XM/XL ParalLine
Power System Data
2
0.00..8.00
0.00
Mutual Parallel Line comp. ratio XM/XL
1128
RATIO Par. Comp
Power System Data
2
50..95 %
85 %
Neutral current RATIO Parallel Line
Comp
1130A
PoleOpenCurrent
Power System Data
2
0.05..1.00 A
0.10 A
Pole Open Current Threshold
1131A
PoleOpenVoltage
Power System Data
2
2..70 V
30 V
Pole Open Voltage Threshold
1132A
SI Time all Cl.
Power System Data
2
0.01..30.00 sec
0.05 sec
Seal-in Time after ALL closures
1134
Line Closure
Power System Data
2
Manual Close BI only
Current OR Voltage or Man-
ual close BI
CBaux OR Current or Man-
ual close BI
Current flow or Manual close
BI
Manual Close BI only
Recognition of Line Closures with
1135
Reset Trip CMD
Power System Data
2
with Pole Open Current
Threshold only
with CBaux AND Pole Open
Current
with Pole Open Current
Threshold only
RESET of Trip Command
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...