Installation and Commissioning
8-50
7SA6 Manual
C53000-G1176-C156-2
8.3.3
Checking the Binary Inputs and Outputs
Preliminary Notes
The binary inputs, outputs, and LEDs of a SIPROTEC
®
4 device can be individually
and precisely controlled using DIGSI
®
4. This feature is used to verify control wiring
from the device to plant equipment during commissioning. This test feature shall not
be used while the device is in service on a live system.
Note:
After termination of the hardware test, the device will reboot. Thereby, all annun-
ciation buffers are erased. If required, these buffers should be extracted with DIGSI
®
4
prior to the test.
The hardware test can be done using DIGSI
®
4 in the online operating mode:
G
Open the
Online
directory by double-clicking; the operating functions for the de-
vice appear.
G
Click on
Test
; the function selection appears in the right half of the screen.
G
Double-click in the list view on
Hardware Test
. The dialogue box of the same
name opens (see Figure 8-26).
Figure 8-26 Dialogue box for hardware test — example
Structure of the
Test Dialogue Box
The dialogue box is divided into three groups:
BI
for binary inputs,
REL
for output
relays, and
LED
for light-emitting diodes. Each of these groups is associated with an
DANGER!
Changing the status of a binary input or output using the test feature of DIGSI
®
4
results in an actual and immediate corresponding change in the SIPROTEC
®
de-
vice. Connected equipment such as circuit breakers or disconnectors will be
operated as a result of these actions!
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...