Functions
6-135
7SA6 Manual
C53000-G1176-C156-2
6.7.3
Settings
Note:
The indicated secondary current values for setting ranges and default settings
refer to I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied
by 5.
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
Addr.
Setting Title
Setting Options
Default Setting
Comments
3101
FCT EarthFltO/C
ON
OFF
ON
Earth Fault overcurrent function
is
3102
BLOCK for Dist.
with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
with every Pickup
Block E/F for Distance protection
3103
BLOCK 1pDeadTim
YES
NO
YES
Block E/F for 1pole Dead time
3104A
Iph-STAB. Slope
0..30 %
10 %
Stabilisation Slope with Iphase
3105
3IoMin Teleprot
0.01..1.00 A
0.50 A
3Io-Min threshold for Teleprot.
schemes
3105
3IoMin Teleprot
0.003..1.000 A
0.500 A
3Io-Min threshold for Teleprot.
schemes
3170
2nd InrushRest
10..45 %
15 %
2nd harmonic ratio for inrush
restraint
3171
Imax InrushRest
0.50..25.00 A
7.50 A
Max.Current, overriding inrush
restraint
3172
SOTF Op. Mode
with Pickup (non-directional)
with Pickup and direction
with Pickup and
direction
Instantaneous mode after Swit-
chOnToFault
3173
SOTF Time DELAY
0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
3110
Op. mode 3I0>>>
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3111
3I0>>>
0.50..25.00 A
4.00 A
3I0>>> Pickup
3112
T 3I0>>>
0.00..30.00 sec;
∞
0.30 sec
T 3I0>>> Time delay
3113
3I0>>> Telep/BI
NO
YES
NO
Instantaneous trip via Teleprot./
BI
3114
3I0>>>SOTF-Trip
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
3115
3I0>>>InrushBlk
NO
YES
NO
Inrush Blocking
3120
Op. mode 3I0>>
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3121
3I0>>
0.20..25.00 A
2.00 A
3I0>> Pickup
3122
T 3I0>>
0.00..30.00 sec;
∞
0.60 sec
T 3I0>> Time Delay
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...