Configuration
5-44
7SA6 Manual
C53000-G1176-C156-2
The utilized processor capacity which is available for the CFC can be checked under
Option
→
Reports
in the register
Check consistency
. By scrolling, an area is
reached, where information regarding the cumulated memory consumption of the
memory reserved for CFC can be read in percent. Figure 5-40 is an example showing
an over-utilization by 56 % in the task level PLC_BEARB (marked in the Figure), while
the other task levels are within the permissible range.
Figure 5-40
Read-out of the CFC configuration degree of utilization
If the limits are exceeded during configuration of the CFC, DIGSI
®
4 issues a warning
(refer to Figure 5-41). After acknowledgement of this alarm, the system utilisation can
be viewed as described above.
Figure 5-41
Warning message on reaching the limits
Table 5-6
Processing times in TICKS required by the individual elements
Individual Element
Amount of TICKS
Module, basic requirement
5
each input more than 3 inputs for generic modules
1
Connection to an input
6
Connection to an output signal
7
Additional for each configuration sheet
1
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...