Installation and Commissioning
8-41
7SA6 Manual
C53000-G1176-C156-2
8.2
Checking the Connections
8.2.1
Data Connections
The following tables list the pin-assignments for the various serial interfaces of the de-
vice and the time synchronization interface.
PC Operating
Interface at Front
When the recommended communication cable is used, correct connection between
the SIPROTEC
®
device and the PC is automatically ensured. See the Appendix, Sub-
section for an ordering description of the cable.
System (SCADA)
Interface
When a serial interface of the device is connected to a central substation control sys-
tem, the data connection must be checked. A visual check of the transmit channel and
the receive channel is important. Each connection is dedicated to one transmission di-
rection. The data output of one device must be connected to the data input of the other
device, and vice versa.
The data cable connections are designated in sympathy with DIN 66020 and ISO
2110 (see also Table 8-24):
−
TxD
data transmit
−
RxD
data receive
−
RTS
request to send
−
CTS
clear to send
−
DGND
signal/chassis ground
The cable shield is to be grounded at both ends so that potential differences cannot
cause circulating currents to flow along the shield.
The physical arrangement of the connectors is illustrated in Sub-section 2.1.5, Figure
2-20.
*) Pin 7 also may carry the RS 232 RTS signal to an RS485 interface. Pin 7 must therefore
not be connected!
Table 8-24
Installation of the D-subminiature ports
Pin No.
Operating
interface
RS232
RS485
Profibus FMS Slave, RS 485
1
Shield (with shield ends electrically connected)
2
RxD
RxD
–
–
3
TxD
TxD
A/A' (RxD/TxD–N)
B/B' (RxD/TxD–P)
4
–
–
–
CNTR–A (TTL)
5
DGND
DGND
C/C' (DGND)
C/C' (DGND)
6
–
–
–
+5 V (max. load 100 mA)
7
RTS
RTS
–*)
–
8
CTS
CTS
B/B' (RxD/TxD–P)
A/A' (RxD/TxD–N)
9
–
–
–
–
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...