6.16.4 Information Overview
3741
U2>(>)
OFF
Alarm Only
ON
OFF
Operating mode U2 overvoltage
prot.
3742
U2>
2.0..220.0 V;
∞
30.0 V
U2> Pickup
3743
T U2>
0.00..30.00 sec;
∞
2.00 sec
T U2> Time Delay
3744
U2>>
2.0..220.0 V;
∞
50.0 V
U2>> Pickup
3745
T U2>>
0.00..30.00 sec;
∞
1.00 sec
T U2>> Time Delay
3749A
U2>(>) RESET
0.50..0.98
0.98
U2>(>) Reset ratio
3751
Uph-e<(<)
OFF
Alarm Only
ON
OFF
Operating mode Uph-e under-
voltage prot.
3752
Uph-e<
1.0..100.0 V; 0
30.0 V
Uph-e< Pickup
3753
T Uph-e<
0.00..30.00 sec;
∞
2.00 sec
T Uph-e< Time Delay
3754
Uph-e<<
1.0..100.0 V; 0
10.0 V
Uph-e<< Pickup
3755
T Uph-e<<
0.00..30.00 sec;
∞
1.00 sec
T Uph-e<< Time Delay
3758
CURR.SUP. Uphe<
ON
OFF
ON
Current supervision (Uph-e)
3761
Uph-ph<(<)
OFF
Alarm Only
ON
OFF
Operating mode Uph-ph under-
voltage prot.
3762
Uph-ph<
1.0..175.0 V; 0
50.0 V
Uph-ph< Pickup
3763
T Uph-ph<
0.00..30.00 sec;
∞
2.00 sec
T Uph-ph< Time Delay
3764
Uph-ph<<
1.0..175.0 V; 0
17.0 V
Uph-ph<< Pickup
3765
T Uphph<<
0.00..30.00 sec;
∞
1.00 sec
T Uph-ph<< Time Delay
3768
CURR.SUP.Uphph< ON
OFF
ON
Current supervision (Uph-ph)
3771
U1<(<)
OFF
Alarm Only
ON
OFF
Operating mode U1 undervol-
tage prot.
3772
U1<
1.0..100.0 V; 0
30.0 V
U1< Pickup
3773
T U1<
0.00..30.00 sec;
∞
2.00 sec
T U1< Time Delay
3774
U1<<
1.0..100.0 V; 0
10.0 V
U1<< Pickup
3775
T U1<<
0.00..30.00 sec;
∞
1.00 sec
T U1<< Time Delay
3778
CURR.SUP.U1<
ON
OFF
ON
Current supervision (U1)
F.No.
Alarm
Comments
10201 >Uph-e>(>) BLK
>BLOCK Uph-e>(>) Overvolt. (phase-earth)
10202 >Uph-ph>(>) BLK
>BLOCK Uph-ph>(>) Overvolt (phase-phase)
Addr.
Setting Title
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...