Installation and Commissioning
8-40
7SA6 Manual
C53000-G1176-C156-2
8.1.3.5
Reassembly of Device
To reassemble the device, proceed as follows:
o
Carefully insert the boards into the case. The installation locations of the boards are
shown in Figure 8-9 to 8-11.
For the model of the device designed for surface mounting, use the metal lever to in-
sert the processor circuit board C-CPU-2 board. The installation is easier with the le-
ver.
o
First plug the plug connectors of the ribbon cable into the input/output boards I/O and
then onto the processor module C-CPU-2. Be careful to not bend any of the connect-
ing pins! Do not use force!
o
Insert the plug connector of the ribbon cable between the processor module
C-CPU-2 and the front cover into the socket of the front cover.
For the version with detached operator panel the latter is to be ignored. Instead the
plug connector of the ribbon cable connected to a 68pole plug connector on the rear
side of the device must be plugged into the plug connector of the processor circuit
board C-CPU-2. The 7-pole plug connector X16 connected to the ribbon cable must
be plugged behind the D-subminiature female connector. Since the connection is pro-
tected against polarity reversal, no particular plug-in position must be observed.
o
Press the latches of the plug connectors together.
o
Replace the front cover and secure to the housing with the screws.
o
Replace the covers.
o
Re-fasten the interfaces on the rear of the device housing.
This activity is not necessary if the device is designed for surface mounting.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...