Functions
6-268
7SA6 Manual
C53000-G1176-C156-2
Since an overload usually occurs in a balanced way, this setting is of minor impor-
tance. If unbalanced overloads are to be expected, however, these options lead to dif-
ferent results.
Averaging should only be used if a rapid thermal equilibrium is possible in the protect-
ed object, e.g. with belted cables. If the three phases are, however, more or less ther-
mally isolated (e.g. single conductor cables or overhead lines), one of the maximum
settings should be chosen at any rate.
6.19.3 Settings
Note:
The indicated secondary current for setting ranges and default settings refer to
I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied by 5.
6.19.4 Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
4201
Ther. OVERLOAD
OFF
ON
Alarm Only
OFF
Thermal overload protection
4202
K-FACTOR
0.10..4.00
1.10
K-Factor
4203
TIME CONSTANT
1.0..999.9 min
100.0 min
Time constant
4204
Θ
ALARM
50..100 %
90 %
Thermal Alarm Stage
4205
I ALARM
0.10..4.00 A
1.00 A
Current Overload Alarm setpoint
4206
CALC. METHOD
Theta Max
Average Theta
Theta from Imax
Theta Max
Method of Acquiring Tempera-
ture
F.No.
Alarm
Comments
1503
>BLK ThOverload
>BLOCK Thermal Overload Protection
1511
Th.Overload OFF
Thermal Overload Protection OFF
1512
Th.Overload BLK
Thermal Overload Protection BLOCKED
1513
Th.O/L ACTIVE
Thermal Overload Protection ACTIVE
1515
Th.O/L I Alarm
Th. Overload: Current Alarm (I alarm)
1516
Th.O/L
Θ
Alarm
Th. Overload Alarm: Near Thermal Trip
1517
Th.O/L Pickup
Th. Overload Pickup before trip
1521
Th.O/L TRIP
Th. Overload TRIP command
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...