Functions
6-244
7SA6 Manual
C53000-G1176-C156-2
Correction of
Measured Values
for Load Current on
Double-end Fed
Lines
When faults occur on loaded lines fed from both ends (Figure 6-119), the fault voltage
U
F1
is influenced not only by the source voltage E
1
but also by the source voltage E
2
,
when both voltages are applied to the common earth resistance R
F
. If not corrected,
this will result in inaccuracies in the calculated impedance, since the current compo-
nent
I
F2
cannot be seen at the measuring point M. For long heavily loaded lines, this
can give a significant error in the X–component of the fault impedance (the determin-
ing factor for the distance-to-fault calculation).
A load compensation feature is provided for the fault location calculation which cor-
rects this measurement inaccuracy. Correction for the R–component of the fault im-
pedance is not possible; but the resultant inaccuracy is not critical, since only the X–
component is critical for the distance to fault indication.
Load compensation is effective for single–phase faults. For single–phase to earth
faults, positive and zero phase sequence components of the symmetrical components
are used in the compensation.
Load compensation can be switched on or off for the fault locator (address
3806
,
Load Compensat.
). Off-switching is useful, for example, during relay testing, in or-
der to avoid influences caused by the test quantities.
Figure 6-119 Fault currents and voltages on double–end fed lines
6.17.2 Applying the Function Parameter Settings
The fault location function is only in service if it was selected to
Enabled
during the
configuration of the device functions (Section 5.1, address
138
).
If the fault location calculation is to be started by the trip command of the protection,
address
3802
START
=
TRIP
is set. In this case a fault location is only output if the
device has also issued a trip. The fault location calculation can however also be start-
ed with each fault detection of the device (address
3802
START
=
PICKUP
). In this
E
1
Z
S1
Z
F1
Z
F2
Z
S2
E
2
M
R
F
I
F1
+
I
F2
I
F1
I
F2
U
F1
Z
S1E
Z
F1E
Z
F2E
Z
S2E
Legend:
M
Measuring location
Z
S1
, Z
S2
Source impedances
E
1
, E
2
Source voltages (EMF)
Z
S1E
, Z
S2E
Earth source impedances
U
F1
Fault voltage at the measuring location
Z
F1
, Z
F2
Fault impedances
I
F1
, I
F2
Part fault currents
Z
F1E
, Z
F2E
Earth fault impedances
I
F1
+ I
F2
Total fault current
R
F
Common fault resistance
~
~
~
~
~
~
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...