Technical Data
10-16
7SA6 Manual
C53000-G1176-C156
Voltage and angle-dependent current pickup (U/I/
ϕ
)
Characteristic
different steps with settable inclinations
Minimum current Iph>
0.10 A to 4.00 A
1
) (steps 0.01 A)
Current in fault angle range I
ϕ
>
0.10 A to 2.00 A
1
) (steps 0.01 A)
Undervoltage phase–earth Uphe
20 V to 70 V (steps 1 V)
Undervoltage phase–phase Uphph
40 V to 130 V (steps 1 V)
(segregated for Iph> and I
ϕ
> and Iph>>)
Lower threshold angle
ϕ
>
30° to 60°
(steps 1°)
Upper threshold angle
ϕ
<
90° to 120° (steps 1°)
Drop-off to pick-up ratio
Iph>, I
ϕ
>,
approx. 0.95
Uphe, Uphph
approx. 1.05
Measuring tolerances for sinusoidal
measured values
values of U, I
± 5 %
angles
ϕ
± 3°
Impedance starting
Minimum current Iph>
0.10 A to 4.00 A
1
)
(steps 0.01 A)
The thresholds of the polygon set to the highest level are relevant taking into consid-
eration the corresponding direction
Drop-off to pick-up ratio
approx. 1.05
*) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied with 5.
Distance
Measurement
Characteristic
polygonal
5 independent and 1 controlled zone
Setting ranges polygon:
I
Ph
> = min. current, phases
0.10 A to 4.00 A
1)
(steps 0.01·A)
X
= reactance reach
0.05
Ω
to 250.00
Ω
2)
(steps 0.001
Ω
)
R
= resistance tolerance phase–phase0.05
Ω
to 250.00
Ω
2)
(steps 0.001
Ω
)
RE = resistance tolerance phase–earth 0.05
Ω
to 250.00
Ω
2)
(steps 0.001
Ω
)
ϕ
Line
= line angle
30° to 89°
(steps 1°)
α
Pol
= tilt angle for 1st zone
0° to 30°
(steps 1°)
Direction determination for polygonal characteristic:
for all types of fault
with phase-true, memorizedor quadrature
voltages
Each zone can be set to forward, reverse or non-directional
Load trapezoid:
R
load
= minimum load resistance
0.10
Ω
to 250.00
Ω
2)
;
∞
(steps 0.001
Ω
)
ϕ
load
= maximum load angle
20° to 60°
(steps 1°)
Drop-off to pick-up ratios
approx. 1.06
Measured value correction
mutual impedance matching for parallel
lines (ordering option)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...