Appendix
B-16
7SA6 Manual
C53000-G1176-C156-2
3430
AR TRIP 3pole
Automatic Reclo-
sure
YES
NO
YES
3pole TRIP by AR
3431
DLC or RDT
Automatic Reclo-
sure
Without
Reduced Dead Time (RDT)
Dead Line Check (DLC)
Without
Dead Line Check or Reduced Dead
Time
3433
T-ACTION ADT
Automatic Reclo-
sure
0.01..300.00 sec;
∞
0.20 sec
Action time
3434
T-MAX ADT
Automatic Reclo-
sure
0.50..3000.00 sec
5.00 sec
Maximum dead time
3435
ADT 1p allowed
Automatic Reclo-
sure
YES
NO
NO
1pole TRIP allowed
3436
ADT CB? CLOSE
Automatic Reclo-
sure
YES
NO
NO
CB ready interrogation before reclos-
ing
3437
ADT SynRequest
Automatic Reclo-
sure
YES
NO
NO
Request for synchro-check after 3pole
AR
3438
T U-stable
Automatic Reclo-
sure
0.10..30.00 sec
0.10 sec
Supervision time for dead/ live voltage
3440
U-live>
Automatic Reclo-
sure
30..90 V
48 V
Voltage threshold for live line or bus
3441
U-dead<
Automatic Reclo-
sure
2..70 V
30 V
Voltage threshold for dead line or bus
3450
1.AR: START
Automatic Reclo-
sure
YES
NO
YES
Start of AR allowed in this cycle
3451
1.AR: T-ACTION
Automatic Reclo-
sure
0.01..300.00 sec;
∞
0.20 sec
Action time
3453
1.AR Tdead 1Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3454
1.AR Tdead 2Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3455
1.AR Tdead 3Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3456
1.AR Tdead1Trip
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 1pole trip
3457
1.AR Tdead3Trip
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3458
1.AR: Tdead EV.
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3459
1.AR: CB? CLOSE
Automatic Reclo-
sure
YES
NO
NO
CB ready interrogation before reclos-
ing
3460
1.AR SynRequest
Automatic Reclo-
sure
YES
NO
NO
Request for synchro-check after 3pole
AR
3461
2.AR: START
Automatic Reclo-
sure
YES
NO
NO
AR start allowed in this cycle
3462
2.AR: T-ACTION
Automatic Reclo-
sure
0.01..300.00 sec;
∞
0.20 sec
Action time
3464
2.AR Tdead 1Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3465
2.AR Tdead 2Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
Automatic Reclo-
sure
0.01..1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...