Control During Operation
7-36
7SA6 Manual
C53000-G1176-C156-2
Double click on
Change Group
. The
Change Group
window is opened, as shown
in Figure 7-36.
Figure 7-36
Setting group switching in DIGSI
®
4
The active setting group is displayed. To switch to another setting group, click on the
field
Value
and select the desired option from the drop-down list. Before closing the
window, transfer the change to the device. This is done by clicking on the button
Digsi
→
Device
. A request for Password No. 7 (password for setting groups) is
given. Enter the correct password, and then click on
OK
.
7.2.3
Test Messages to the System (SCADA) Interface during Test Operation
Depending on the type of protocol, all messages and measured values transferred to
the central control system can be identified with an added message “test operation”-
bit while the device is being tested onsite (test mode). This identification prevents the
messages from being incorrectly interpreted as resulting from an actual power system
disturbance or event. As another option, all messages and measured values normally
transferred via the SCADA interface can be blocked during the testing (block data
transmission).
A password for test and diagnostics is required (password no. 4) to block the messag-
es and measured values.
Data transmission block can be accomplished by controlling binary inputs, by using
the operating panel on the device, or via DIGSI
®
4.
If binary inputs are used, then the appropriate inputs must be configured.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...