Control During Operation
7-23
7SA6 Manual
C53000-G1176-C156-2
From PC with
DIGSI
®
4
Set points are only available in online–mode. The metered value groups are to be
found under
Measurement
(Figure 7-2) by double-clicking on the latter. Select
Other
and then
Set Points (Measured Values)(
Figure 7-24).
By double clicking on an entry in the list in the right part of the window, the set points
are loaded. Mark the number of the value which is to be changed. With a right mouse
click, open the context menu and click on
Set
,
as shown in Figure 7-24. A password
inquiry (password No 5 for individual settings) occurs. Next, the dialog field
Set Me-
tered Value
is opened. Enter the desired value in the entry field. Then click on
OK
.
The entered value is transferred to the device and the display within the window in Fig-
ure 7-24 is updated.
Figure 7-24
Set Points in DIGSI
®
4
: