Functions
6-31
7SA6 Manual
C53000-G1176-C156-2
Figure 6-17
Logic of the earth fault recognition
Earth Fault
Recognition during
Single-Pole Open
Condition
The earth fault recognition is modified during the single-pole open condition with
single-pole automatic reclosure in an earthed system (Figure 6-18). In this case, the
magnitudes of the currents and voltages are monitored in addition to the angles be-
tween the currents.
Figure 6-18
Earth fault recognition during single-pole open condition
Earth Fault Detec-
tion
for Non-Earthed
Systems
In non-earthed systems (isolated system star point or resonant-earthed by means of
a Peterson coil) the measured displacement voltage is not used for fault detection.
Furthermore, in these systems a simple earth fault is assumed initially in case of a sin-
gle-phase fault and the fault detection is suppressed in order to avoid an erroneous
pickup as a result of the earth fault initiation transients. After a time delay
T3I0
1PHAS
,
which can be set,
the fault detection is released again; this is necessary for
the distance protection to still be able to detect a double earth fault with one base point
on a dead-end feeder.
If, however, an earth fault is already present in the system, it is detected by the dis-
placement voltage detection (
3U0> COMP/ISOL.
). In this case, there is no delay
time: an earth fault now occurring in a different phase can only be due to a double
earth fault. If, apart from the displacement measurement (
3U0> COMP/ISOL.
), there
is a fault detection in more than one phase, this is also rated as a double earth fault.
In this way, double earth faults can be detected even if no or only little earth current
flows via the measuring point.
3
I
0
3
I
2
3
I
2
≥
1
3U
0
3I
0
I
Ph
3I
0
3V0>
I
Ph
1203
3I0>
1204
3U0>
earth fault
&
&
≥
1
max(I
Lx
, I
Ly
)
<
2
·min(I
Lx
, I
Ly
)
max(U
Lx
,
U
Ly
)
<
1.5
·min(U
Lx
, U
Ly
)
Angle criteria
3I
0
>
1203 3I0>
&
3I
0
I
Lx
earth fault
I
Ly
U
Lx–E
U
Ly–E
for load condition
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...