Region-Specific Default/Language Settings and Function Versions
Region GE, language German (language can be changed)
A
Region world, language English (GB) (language can be changed)
B
Region US, language English (USA) (language can be changed)
C
Region FR, 50 Hz, IEC, French language (may be changed)
D
Region World, 50/60 Hz, IEC/ANSI, Spanish language (may be changed)
E
Region World, 50/60 Hz, IEC/ANSI, Italian language (may be changed)
F
Regulations for Region-Specific Default and Function Settings:
Region World:
Preset to f = 50 Hz and line length in km
Region US:
Preset to f = 60 Hz and line length in miles, ANSi inverse characteristic only
Region FR:
Preset to f = 50 Hz and line length in km, IEC inverse characteristic available,
no STUB-Bus stage available, no logical inverse characteristic for earth fault protection
available
Port B
Not installed
0
System port, IEC protocol, electrical RS232
1
System port, IEC protocol, electrical RS485
2
System port, IEC protocol, optical 820 nm, ST-connector
3
System port, Profibus FMS Slave, electrical RS485
4
System port, Profibus FMS Slave, optical, single-ended ring, ST-connector
5
System port, Profibus FMS Slave, optical, double-ended ring, ST-connector
6
Analog Output 2 x 0 to 20 mA
7
For further protocols see additional information “L”
9
Port B
System port, Profibus DP Slave, electrical RS485
0 A
System port, Profibus DP Slave, optical 820 nm, double-ended ring, ST-connector
0 B
System port, DNP3.0, electrical RS485
0 G
System port, DNP3.0, optical 820 nm, double-ended ring, ST-connector
0 H
Port C and Port D
DIGSI/modem, electrical RS232, port C
1
DIGSI/modem, electrical RS485, port C
2
With port C and D see addtional information “M”
9
Port C
DIGSI/modem, electrical RS232
1
DIGSI/modem, electrical RS485
2
Port D; for 1.) Direct Connection; 2.) Communication Networks
Optical 820 nm, 2-ST-connector, length of optical fibre up to 1.5 km for multimode-fibre (FO5); 1.) or 2.)
A
Optical 820 nm, 2-ST-connector, length of optical fibre up to 3.5 km for multimode-fibre (FO6); 1.);
B
Optical 1300 nm, 2-ST-connector, length of optical fibre up to 10 km for monomode-fibre (FO7); 1.)
C
Optical 1300 nm, 2-FC-connector, length of optical fibre up to 35 km for monomode-fibre (FO8); 1.)
D
Analog output
Analog Output 2 x 0 to 20 mA (Port D)
K
see page A-8
_
7SA6
7
8
13
15 16
14
_
9 10 11 12
Distance Protection (position 10 to 12)
6
5
M
+
L
+
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...