Appendix
B-14
7SA6 Manual
C53000-G1176-C156-2
3141
3I0p PICKUP
Earth fault overcur-
rent
0.003..25.000 A
1.000 A
3I0p Pickup
3142
3I0p MinT-DELAY
Earth fault overcur-
rent
0.00..30.00 sec
1.20 sec
3I0p Minimum Time Delay
3143
3I0p Time Dial
Earth fault overcur-
rent
0.05..3.00 sec;
∞
0.50 sec
3I0p Time Dial
3144
3I0p Time Dial
Earth fault overcur-
rent
0.50..15.00;
∞
5.00
3I0p Time Dial
3145
3I0p Time Dial
Earth fault overcur-
rent
0.05..15.00 sec;
∞
1.35 sec
3I0p Time Dial
3146
3I0p MaxT-DELAY
Earth fault overcur-
rent
0.00..30.00 sec
5.80 sec
3I0p Maximum Time Delay
3147
Add.T-DELAY
Earth fault overcur-
rent
0.00..30.00 sec;
∞
1.20 sec
Additional Time Delay
3148
3I0p Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3149
3I0p SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3150
3I0p InrushBlk
Earth fault overcur-
rent
NO
YES
NO
Inrush Blocking
3151
IEC Curve
Earth fault overcur-
rent
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
IEC Curve
3152
ANSI Curve
Earth fault overcur-
rent
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
ANSI Curve
3153
LOG Curve
Earth fault overcur-
rent
Logarithmic inverse
Logarithmic inverse
LOGARITHMIC Curve
3154
3I0p Startpoint
Earth fault overcur-
rent
1.0..4.0
1.1
Start point of inverse characteristic
3160
POLARIZATION
Earth fault overcur-
rent
with U0 and IY (dual polar-
ized)
with IY (transformer star
point current)
with U2 and I2 (negative
sequence)
with U0 and IY (dual polar-
ized)
Polarization
3162A
Dir. ALPHA
Earth fault overcur-
rent
0..360
°
338
°
ALPHA, lower angle for forward direc-
tion
3163A
Dir. BETA
Earth fault overcur-
rent
0..360
°
122
°
BETA, upper angle for forward direc-
tion
3164
3U0>
Earth fault overcur-
rent
0.5..10.0 V
0.5 V
Min. zero seq.voltage 3U0 for polariz-
ing
3165
IY>
Earth fault overcur-
rent
0.05..1.00 A
0.05 A
Min. earth current IY for polarizing
3166
3U2>
Earth fault overcur-
rent
0.5..10.0 V
0.5 V
Min. neg. seq. polarizing voltage 3U2
3167
3I2>
Earth fault overcur-
rent
0.05..1.00 A
0.05 A
Min. neg. seq. polarizing current 3I2
3170
2nd InrushRest
Earth fault overcur-
rent
10..45 %
15 %
2nd harmonic ratio for inrush restraint
3171
Imax InrushRest
Earth fault overcur-
rent
0.50..25.00 A
7.50 A
Max.Current, overriding inrush
restraint
3172
SOTF Op. Mode
Earth fault overcur-
rent
with Pickup (non-directional)
with Pickup and direction
with Pickup and direction
Instantaneous mode after Switch-
OnToFault
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...