Functions
6-261
7SA6 Manual
C53000-G1176-C156-2
Figure 6-136 Time sequence example for normal clearance of a fault, and with circuit breaker
failure, using two-stage breaker failure protection
Single-stage
Breaker Failure
Protection
With single-stage operation, the adjacent circuit breakers (i.e. the breakers of the bus-
bar zone and — if transmission of the signal is possible — the breaker at the remote
end) are tripped after a delay time
T2
(address
3906
) following initiation, should the
fault not have been cleared within this time.
The timers
T1-1pole
(address
3904
) and
T1-3pole
(address
3905
) are then set to
∞
since they are not needed.
But you may use the T1-timers for single-stage protection if you wish to utilize the fa-
cility of setting different delay times after single-pole trip and three-pole trip of the feed-
er protection. In this case, set the desired times under addresses
3904
T1-1pole
and
3905
T1-3pole
but set address
3903
1p-RETRIP (T1)
to
No
to avoid a single-
pole trip to the bus-bar. And set
T2
(address
3906
) to
∞
or equal to
T1-3pole
. Be
sure that the correct trip commands are assigned to the desired trip relay(s).
The delay times are determined from the maximum operating time of the feeder circuit
breaker, the reset time of the current detectors of the breaker failure protection, plus
a safety margin which allows for any tolerance of the delay timers. The time sequence
is illustrated in Figure 6-137. For sinusoidal currents one can assume that the reset
time of the current detectors is less than 12 ms but if current transformer saturation is
expected then 25 ms should be assumed.
Fault inception
Fault clearance time normal
Prot.
trip
CB operating time
(local)
Reset
I–BF
Safety
margin
CB operating time
(adjacent CBs)
Initiation breaker
failure protection
Time delay T1 of breaker
failure protection
Trip command
repetition
Reset
I> BF
Safety
margin
Time delay T2 of breaker
failure protection
Total fault clearance time with breaker failure
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...