Appendix
B-11
7SA6 Manual
C53000-G1176-C156-2
2635
I-STUB SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2640
Ip>
Backup overcurrent 0.10..4.00 A;
∞
∞
A
Ip> Pickup
2642
T Ip Time Dial
Backup overcurrent 0.05..3.00 sec;
∞
0.50 sec
T Ip Time Dial
2643
Time Dial TD Ip
Backup overcurrent 0.50..15.00;
∞
5.00
Time Dial TD Ip
2646
T Ip Add
Backup overcurrent 0.00..30.00 sec
0.00 sec
T Ip Additional Time Delay
2650
3I0p PICKUP
Backup overcurrent 0.05..4.00 A;
∞
∞
A
3I0p Pickup
2652
T 3I0p TimeDial
Backup overcurrent 0.05..3.00 sec;
∞
0.50 sec
T 3I0p Time Dial
2653
TimeDial TD3I0p
Backup overcurrent 0.50..15.00;
∞
5.00
Time Dial TD 3I0p
2656
T 3I0p Add
Backup overcurrent 0.00..30.00 sec
0.00 sec
T 3I0p Additional Time Delay
2660
IEC Curve
Backup overcurrent Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
IEC Curve
2661
ANSI Curve
Backup overcurrent Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
ANSI Curve
2670
I(3I0)p Tele/BI
Backup overcurrent NO
YES
NO
Instantaneous trip via Teleprot./BI
2671
I(3I0)p SOTF
Backup overcurrent NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
2680
SOTF Time DELAY Backup overcurrent 0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
2801
DMD Interval
Demand Measure-
ment Setup
15 Min per., 1 Sub
15 Min per., 3 Subs
15 Min per., 15 Subs
30 Min per., 1 Sub.
60 Min per., 1 Sub.
60 Min per., 1 Sub.
Demand Calculation Intervals
2802
DMD Sync.Time
Demand Measure-
ment Setup
On the Hour
15 Min. after Hour
30 Min. after Hour
45 Min. after Hour
On the Hour
Demand Synchronization Time
2811
MinMax cycRESET Min/Max Measure-
ment Setup
NO
YES
YES
Automatic Cyclic Reset Function
2812
MiMa RESET TIME Min/Max Measure-
ment Setup
0..1439 min
0 min
MinMax Reset Timer
2813
MiMa RESETCY-
CLE
Min/Max Measure-
ment Setup
1..365 day(s)
7 day(s)
MinMax Reset Cycle Period
2814
Min-
MaxRES.START
Min/Max Measure-
ment Setup
1..365 Days
1 Days
MinMax Start Reset Cycle in
2901
MEASURE.
SUPERV
Measurement
Supervision
ON
OFF
ON
Measurement Supervision
2902A
BALANCE U-LIMIT Measurement
Supervision
10..100 V
50 V
Voltage Threshold for Balance Moni-
toring
2903A
BAL. FACTOR U
Measurement
Supervision
0.58..0.95
0.75
Balance Factor for Voltage Monitor
2904A
BALANCE I LIMIT
Measurement
Supervision
0.10..1.00 A
0.50 A
Current Balance Monitor
2905A
BAL. FACTOR I
Measurement
Supervision
0.10..0.95
0.50
Balance Factor for Current Monitor
2906A
Σ
I THRESHOLD
Measurement
Supervision
0.05..2.00 A
0.10 A
Summated Current Monitoring Thresh-
old
2907A
Σ
I FACTOR
Measurement
Supervision
0.00..0.95
0.10
Summated Current Monitoring Factor
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...