Configuration
5-46
7SA6 Manual
C53000-G1176-C156-2
•
The number of inputs of the AND gate is increased to 7.
•
The CLOSE indications from the circuit breaker (CB) and from the grounding switch
(GS) are supplied to the inputs of the NOR functions.
•
The OPEN indications from the circuit breaker (CB) and from the grounding switch
(GS) are supplied to the inputs of the AND function.
•
The switch position indications from the disconnect switch (IS) are linked to the in-
puts of the XOR function.
•
The outputs of the NOR and XOR gates are connected to the inputs of the AND
function.
•
Function key 4 is linked with an input of the AND function.
•
The output of the AND gate is linked to the right border column at the switching com-
mand “Disconnector Close”.
Figure 5-43
Interlocking an disconnect switch as an example of a user defined interlock pro-
tective function
Example 3 (PLC1):
Additional Logic
By using slow PLC processing, an additional, event-driven logic condition may be con-
structed which delivers indications regarding switch-gear operating status. These in-
dications may be passed externally via LEDs or relay contacts, or used as input sig-
nals for further logical links. In the example (see Figure 5-44), the output information
indication from the circuit breaker interlocking logic (CB TRIP) and a joint indication
from all protective element trip signals (Protection TRIP) are linked to a new “
Circuit
Breaker Operation
” message. Furthermore, the single point indication (SP)
Test
Oper
, which may be coupled via a binary input, is linked with an internal reusable
“
Test oper.
” message.
&
CB is
CB is
GS is
GS is
IS is
IS is
Door
is CLOSED
Disconnector
≥
1
≥
1
=1
Function
Key 4
Close
CLOSED
OPEN
CLOSED
OPEN
CLOSED
OPEN
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...