Functions
6-273
7SA6 Manual
C53000-G1176-C156-2
5033
20 mA (D2) =
1.0..1000.0 km
50.0 km
20 mA (D2) correspond to
5034
20 mA (D2) =
1.0..1000.0 Miles
50.0 Miles
20 mA (D2) correspond to
5036
MIN VALUE (D2)
0.0..5.0 mA
4.0 mA
Output value (D2) valid from
5037
NEG VALUE (D2)
1.00..22.50 mA
19.84 mA
Output value (D2) for negative
values
5038
OVERFLOW (D2)
1.00..22.50 mA
22.50 mA
Output value (D2) for overflow
5039
Tmax OUTPUT(D2)
0.10..180.00 sec;
∞
5.00 sec
Maximum output time (D2)
Addr.
Setting Title
Setting Options
Default Setting