Functions
6-49
7SA6 Manual
C53000-G1176-C156-2
Figure 6-28
Circuit breaker closure onto a fault
6.2.3.2
Applying the Function Parameter Settings
General Function
Parameters
The distance protection can be switched on or off with the parameter in address
1201
FCT Distance
ON/OFF
The minimum current for fault detection
Minimum Iph>
(address
1202
) is set some-
what (approx. 10 %) below the minimum short-circuit current that may occur.
The setting parameters for the treatment of earth faults
1203
3I0> Threshold
and
1204
3U0> Threshold
were already discussed in Sub-section 6.2.1.2.
Correction of
Measured Values
on Parallel Lines
(optional)
The mutual coupling between the two lines of a double-circuit configuration is only rel-
evant to the 7SA6 when it is applied on a double-circuit line and when it is intended to
implement parallel line compensation. A prerequisite is that the earth current of the
parallel line is connected to the
I
4
measuring input of the 7SA6 and this is entered in
the configuration settings.
In this case, the setting
Paral.Line Comp
=
YES
must be set in address
1215
; oth-
erwise the presetting
NO
remains.
The coupling factors were already set as part of the general protection data (Sub-sec-
tion 6.1.3), as was the reach of the parallel line compensation.
Double Earth Faults
in Earthed Systems
The loop selection for double earth faults is set in address
1221A
2Ph-E faults
(Phase–Phase–Earth–fault detection). This setting can only be modified with DIGSI
®
4 under “Additional Settings”. In general the
Block leading Ø
(blocking of the
leading phase, presetting) is favourable, because the leading phase-earth loop tends
to overreach, especially in conjunction with large earth fault resistance. In certain cas-
es (fault resistance phase-phase larger than phase-earth) the setting
Block lag-
ging
Ø
(blocking of the lagging phase) may be more favourable. The selection of all
affected loops with the setting
All loops
allows a maximum degree of redundancy.
Alternatively,
Ø-Ø loops only
may be evaluated. This ensures the most accuracy
for two phase to earth faults. Ultimately it is possible to declare the
Ø-E loops only
as valid.
Double Earth Faults
in Non-earthed Sys-
tems
In isolated or resonant-earthed systems it must be guaranteed that the preference for
double earth faults in whole galvanically-connected systems is consistent. The double
earth fault preference is set in address
1220
PHASE PREF.2phe
.
Z1B instantaneous.
SOTF zone
Zone Z1B
Inactive
PICKUP
„1“
SOTF Op. mode
≥
1
&
≥
1
&
Z2 instantaneous.
Z3 instantaneous.
Z4 instantaneous.
Z5 instantaneous.
ENABLE Z1B
3611
1232
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...