Appendix
B-13
7SA6 Manual
C53000-G1176-C156-2
3103
BLOCK 1pDeadTim Earth fault overcur-
rent
YES
NO
YES
Block E/F for 1pole Dead time
3104A
Iph-STAB. Slope
Earth fault overcur-
rent
0..30 %
10 %
Stabilisation Slope with Iphase
3105
3IoMin Teleprot
Earth fault overcur-
rent
0.01..1.00 A
0.50 A
3Io-Min threshold for Teleprot.
schemes
3105
3IoMin Teleprot
Earth fault overcur-
rent
0.003..1.000 A
0.500 A
3Io-Min threshold for Teleprot.
schemes
3110
Op. mode 3I0>>>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3111
3I0>>>
Earth fault overcur-
rent
0.50..25.00 A
4.00 A
3I0>>> Pickup
3112
T 3I0>>>
Earth fault overcur-
rent
0.00..30.00 sec;
∞
0.30 sec
T 3I0>>> Time delay
3113
3I0>>> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3114
3I0>>>SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3115
3I0>>>InrushBlk
Earth fault overcur-
rent
NO
YES
NO
Inrush Blocking
3120
Op. mode 3I0>>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3121
3I0>>
Earth fault overcur-
rent
0.20..25.00 A
2.00 A
3I0>> Pickup
3122
T 3I0>>
Earth fault overcur-
rent
0.00..30.00 sec;
∞
0.60 sec
T 3I0>> Time Delay
3123
3I0>> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3124
3I0>> SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3125
3I0>> InrushBlk
Earth fault overcur-
rent
NO
YES
NO
Inrush Blocking
3130
Op. mode 3I0>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3131
3I0>
Earth fault overcur-
rent
0.05..25.00 A
1.00 A
3I0> Pickup
3131
3I0>
Earth fault overcur-
rent
0.003..25.000 A
1.000 A
3I0> Pickup
3132
T 3I0>
Earth fault overcur-
rent
0.00..30.00 sec;
∞
0.90 sec
T 3I0> Time Delay
3133
3I0> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3134
3I0> SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3135
3I0> InrushBlk
Earth fault overcur-
rent
NO
YES
NO
Inrush Blocking
3140
Op. mode 3I0p
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3141
3I0p PICKUP
Earth fault overcur-
rent
0.05..25.00 A
1.00 A
3I0p Pickup
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...