Technical Data
10-21
7SA6 Manual
C53000-G1176-C156
Time factor
T
3I0P
0.05 s to 15.00 s
(steps 0.01 s)
or
∞
(ineffective)
Maximum time
T
3I0P max
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Minimum time
T
3I0P min
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Additional time delay
T
3I0Pverz
0.00 s to 30.00 s
(steps 0.01 s)
characteristics see Figure 10-4
Tolerances
times
5 % ± 15 ms für 2
≤
I/3I
0P
≤
20
und T
3I0P
/s
≥
1
def. times
1 % of set value or 10 ms
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Zero Sequence
Voltage - U
0
inverse
Pickup values
3I
0P
0.05 A to 25.00 A
1
)
(steps 0.01 A)
or
0.003 A bis 25.000 A
1
) (steps 0,001 A)
3U
0
>
1.0 V to 10.0 V
(steps 0.1 V)
Voltage factor
U
0 inv.min
0.1 V to 5 V
(steps 0.1 V)
characteristics see Figure 10-5
Additional delay times
Tforw
0.00 s to 32.00 s
(steps 0.01 s)
Trev
0.00 s to 32.00 s
(steps 0.01 s)
characteristics see Figure 10-5
Tolerances
times
1 % of set value or 10 ms
Drop-off to pick-up ratio current
approx. 0.95 for I/I
N
≥
0.5
voltage
approx. 0.95 for 3U
0
≥
1 V
The set times are pure delay times.
1) Secondary values based on I
N
= 1 A; for I
N
= 5 A the current values must be multiplied by 5.
Inrush Stabilization
Second harmonic content for inrush
10 % to 45 %
(steps 1 %)
blocking
referred to fundamental wave
Inrush blocking is cancelled above
0.50 A to 25.00 A
1
)
(steps 0.01 A)
Inrush stabilization may be switched effective or ineffective for each individual stage.
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied with 5.
Direction
Determination
Direction determination
with I
E
(= 3I
0
) and 3U
0
with I
E
(= 3I
0
)
and I
Y
(transformer star-point current)
with 3I
2
and 3U
2
(negative sequence quantities)
Limit values
Displacement voltage
3U
0
>
0.5 V to 10.0 V
(steps 0.1 V)
Starpoint current of a power
transformer I
Y
>
0.05 A to 1.00 A
1
)
(steps 0.01 A)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...