S-FLS series 

Non-Intrinsic Safety Signal 

  Surge Protective Devices 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

   

 

Nanjing New Power Electric Co., Ltd. 

 

 

 

 

 

 

 

Test standards 

IEC 61643-1/GB 18802.1; IEC 61643-21/GB/T 18802.21 
IEC 62305-1~IEC 62305-5; IEC 61508-1~IEC 61508-7 

 

Model description 

 

 

 
 
 
 
 

 
 
 
 

 

 

Features 

  7.4 mm Ultra-thin design, saving space; 

  Multiple protection circuit, strong resistance to surge; 

  Support terminal grounding (optional); 

  35 mm rail installation; 

  A variety of models, applicable to all measurement. 

 

Parameters 

 

 

Wiring diagram 

 

Unprotected

P r o t e c t e d

1

2

5

6

In

Out

 

S-FLS-2-5, S-FLS-2-24

 

                 

S-FLS-2-5G, S-FLS-2-24G

 

 

1

2

5

6

Unprotected

Protected

3

7

In

Out

1

2

5

6

Unprotected

Protected

3

7

In

Out

 

 S-FLS-3-5, S-FLS-3-24   

             

S-FLS-3-5G, S-FLS-3-24G 

 
 
 
 
 
 
 
 
 
 
 

 

 

Applications 

S-FLS series non-intrinsic safety SPD is used to 
protect signals and control equipments, preventing 
interference caused by lightning or high voltage switch. 
In a short surge impact, by discharging the transient 
current to the ground to clamp the voltage in a safe 
level and ensure the transmission. It guarantees the 
safety for industrial automation equipment. 
This product is a 7.4 mm ultra-thin design with the 
advantages of strong surge resistance, low residual, 
fast response, etc. Moreover, it is easy to use and 
install, can support all kinds of control system, the I/O 
system, communication network equipment, etc. 
 

 

 

 

 

 

Equipotential connection drawing 

 

1

2

3

PE

5

6

7

 

   Connection diagram 

 

Grounding 

It is necessary to ground the SPD correctly. Each 
SPD should be grounding by DIN rail. 

 
 
 
 
 
 
 

 

Type

Parameter 

S-FLS-2-5 

S-FLS-2-24

S-FLS-2-5G

S-FLS-2-24G

S-FLS-3-5 

S-FLS-3-5G

S-FLS-3-24

S-FLS-3-24G

Voltage Un 

5 V 

24 V 

5 V 

24 V 

5 V 

5 V 

24 V 

24 V 

Max. operating voltage Uc 

(DC) 

6 V 

32 V 

6 V 

32 V 

6 V 

6 V 

32 V 

32 V 

nominal current I

L

 

600 mA 

600 mA 

600 mA 

600 mA 

600 mA 

600 mA 

600 mA 

600 mA 

Total discharge current In 

(8/20 

μ

s, C2) 

10 kA 

10 kA 

10 kA 

10 kA 

10 kA 

10 kA 

10 kA 

10 kA 

Discharge current per path 

In (8/20 

μ

s, C2) 

5 kA 

5 kA 

5 kA 

5 kA 

5 kA 

5 kA 

5 kA 

5 kA 

Impulse current 

Iimp (10/350 

μ

s) 

2 kA 

2 kA 

2 kA 

2 kA 

2 kA 

2 kA 

2 kA 

2 kA 

Voltage protection 

Up (8/20 

μ

s, C2) 

L-L 

 45 V 

L-L 

 60 V 

L-L 

 45 V 

L-L 

 60 V 

L-L 

 45V 

L-L 

 45V 

L-L 

 60V 

L-L 

 60 V 

L-PE 

 650 V

L-PE 

 650 V

L-PE 

 45 V

L-PE 

 60 V

L-PE 

 650 V

L-PE 

 45V

L-PE 

 650 V

L-PE 

 60 V

Voltage protection 

Up (1 kV/

μ

s, C3) 

L-L

15 V 

L-L 

 45 V 

L-L 

 15 V 

L-L 

 45 V 

L-L 

 15 V 

L-L 

 15V 

L-L 

 45 V 

L-L 

 45 V 

L-PE 

 650 V

L-PE 

 650 V

L-PE 

 15 V

L-PE 

 45 V

L-PE 

 650 V

L-PE 

 15 V

L-PE 

 650 V

L-PE 

 45 V

Series impedances 

1.8 

 1.8 

 1.8 

 1.8 

 1.8 

 1.8 

 1.8 

 1.8 

 

Limiting frequency (f

G

100 MHz 

10 MHz 

100 MHz 

10 MHz 

10 MHz 

10 MHz 

10 MHz 

10 MHz 

Response time 

<1 ns 

Temperature 

-40 

 ~ +80 

 

Installation 

35 mm DIN rail 

Connections 

rail grounding/terminal grounding (optional) 

Connecting wire size 

0.2 ~ 2.5 mm

2

 

Material 

PC 

    Field

   devices

  (transmitter)

S series

surge

protective

devices

S series

surge

protective

devices

Control

room

device

(DCS or

PLC)

Field

Control room

X

X

X

X

X X

.

X

Explosion proof: blank: non-intrinsic safety

Series: S: S series SPD

Types: FL: lightning protection

Structure: T: 12.4 mm module insert

Input channel 2: 2-wire

;

  3: 3-wire

Voltage: 5: 5 V DC; 24: 24 V DC

Protected mode: blank: floating

                  

S: 7.4 mm; P:field installation

                      4: 4-wire

2D: dual channel

                     Ex: intrinsic safety

                      2S: 2-wire series

;

 3S: 3-wire series

                      2P: 2-wire parallel

;

 3P: 3-wire parallel

                      4P: 4-wire parallel

                     G: grounding

1

2

5

6

Unprotected

Protected

3

7

In

Out

Reviews: