Configuration
5-32
7SA6 Manual
C53000-G1176-C156-2
Figure 5-29
Dialogue box: object properties for a command with feedback
The conditional checks that should be conducted before execution of a switching com-
mand can also be defined:
•
Substation interlocking: interlocking of substations is carried out (configuration via
a substation)
•
Zone controlled (Bay Specific Interlocking): Logic functions in the device created
with CFC are processed for interlocked switching.
•
Switching direction check (scheduled/actual): The switching command is negated
and a corresponding indication is issued if the circuit-breaker is already in the
scheduled position. As soon as this check is activated, the switching direction check
will not only be enabled for interlocked, but also for non-interlocked switching.
•
Blocked by protection: CLOSE commands to the switchgear are blocked as soon
as one of the protective functions in the device picks up a fault. TRIP commands,
in contrast, can always be executed.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...