Technical Data
10-12
7SA6 Manual
C53000-G1176-C156
10.1.7 Climatic Stress Tests
Ambient
Temperatures
Standards:
IEC 60255–6
– recommended operating temperature –5 °C to +55 °C
(+23 °F to +131 °F)
if max. half of the inputs and outputs are subjected
to the max. permissible values
– recommended operating temperature –5 °C to +40 °C
(+23 °F to +104 °F)
if all inputs and outputs are subjected
to the max. permissible values
– limiting temporary (transient)
–20 °C to +70 °C
operating temperature
(–4 °F to 158 °F)
in quiescent state, i.e. no pick-up and no
indications
– limiting temperature during storage
–25 °C to +55 °C
(–13 °F to 131 °F)
– limiting temperature during transport
–25 °C to +70 °C
(–13 °F to 158 °F)
Storage and transport of the device with factory packaging!
Humidity
Permissible humidity
mean value p. year
≤
75 % relative humidity
on 56 days per year up to 93 % relative
humidity; condensation not permissible!
It is recommended that all devices are installed such that they are not exposed to di-
rect sunlight, nor subject to large fluctuations in temperature that may cause conden-
sation to occur.
10.1.8 Service Conditions
The device is designed for use in an industrial environment or an electrical utility en-
vironment, for installation in standard relay rooms and compartments so that proper
installation and electromagnetic compatibility (EMC) is ensured. In addition, the follow-
ing are recommended:
•
All contactors and relays that operate in the same cubicle, cabinet, or relay panel
as the numerical protective device should, as a rule, be equipped with suitable
surge suppression components.
•
For substations with operating voltages of 100 kV and above, all external cables
should be shielded with a conductive shield grounded at both ends. The shield must
be capable of carrying the fault currents that could occur. For substations with lower
operating voltages, no special measures are normally required.
•
Do not withdraw or insert individual modules or boards while the protective device
is energized. When handling the modules or the boards outside of the case, stand-
ards for components sensitive to electrostatic discharge (ESD) must be observed.
The modules, boards, and device are not endangered when the device is complete-
ly assembled.
Visibility of display
may be impaired
above +55 °C/130 °F
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...