Functions
6-2
7SA6 Manual
C53000-G1176-C156-2
6.1
General
A few seconds after the device is switched on, the initial display appears in the LCD.
Depending on the device version either measured values (four-line display) or a sin-
gle-phase switching diagram of the feeder status (graphic display) is displayed in the
7SA6.
The setting parameters can be entered via the keypad and display on the front of the
device, or by means of a personal computer connected to the front or service interface
of the device utilising the DIGSI
®
4 software package. The level 5 password (individ-
ual parameters) is required.
From the
DeviceFront
Select the
MAIN MENU
by pressing the
key. Using the
key, select
Settings
,
and then press the
key to navigate to the
SETTINGS
display (see Figure 6-1).
In the
SETTINGS
display, use the
key to select the desired function, and then use
the
key to navigate to that function (e.g., use the
key to select the
P.System
Data1
function, and then use the
key to navigate to the
P.SYSTEM DATA1
dis-
play, as shown in Figure 6-2.
In general, an item number appears in the menu list to the right of each selection. Nav-
igation can be accomplished using the item number in place of the
and
keys.
This feature is particularly helpful in large menus (e.g., setting lists). Based on the ex-
ample above, from the
MAIN MENU
, the
SETTINGS
display can be reached by press-
ing
on the keypad, and then the
P.SYSTEM DATA1
display can be reached by
pressing
on the keypad.
Figure 6-1
Example of navigation from the front control panel
Each setting contains a four-digit address number followed by the setting title as
shown in Figure 6-2. The value of the current setting is displayed in the line just below
the setting address number and title. The value may be text (Figure 6-2,
Address
0201
) or numerical (Figure 6-2, Address
0202
).
Figure 6-2
Example of power system data display
MENU
4
0
3
SETTINGS 03/11
---------------------
Device Config.–> 01
Masking (I/O) –> 02
P.System Data1–> 03
Group A –> 04
MAIN MENU 04/05
---------------------
Annunciation –> 1
Measurement –> 2
Control –> 3
Settings –> 4
Test/Diagnose –> 5
P.SYSTEM DATA1 01/16
---------------------
0201 CT Starpoint
towards Line
0202 Vnom PRIMARY
12.00kV
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...