Functions
6-303
7SA6 Manual
C53000-G1176-C156-2
Following each trip command the device registers the value of each phase current that
was switched off in each pole. This information is then provided in the trip log and ac-
cumulated in a register. The maximum current that was switched off is also stored.
If the device is equipped with the integrated automatic reclosure, the automatic close
commands are also counted, separately for reclosure after single-pole tripping, after
three-pole tripping as well as separately for the first reclosure cycle and other reclos-
ure cycles.
The counter and register contents are protected against loss of auxiliary voltage. They
may be set to zero or any other initial value. Further information can be obtained in
Subsection 7.1.2.
6.22.5 Circuit Breaker Trip Test
The Distance Protection 7SA6 allows for convenient testing of the trip circuits and the
circuit breaker.
The test programs as shown in Table 6-16 are available. The single-pole tests are nat-
urally only available if the device at hand allows for single-pole tripping. The listed out-
put alarms must be allocated to the corresponding command relays, used for the op-
eration of the circuit breaker trip and close coils, during marshalling as stated in Sub-
section 5.2.3.
The test is initiated via the keypad and display on the front of the device or from a PC
with DIGSI
®
4. The procedure is described in Section 7.3. Figure 6-157 shows the se-
quence of a trip/close test cycle. The timer setting values are according to Sub-section
6.1.1 for “Trip/Close Command Duration” and “Circuit Breaker Test”.
If the auxiliary contacts of the circuit breaker or the individual circuit breaker poles in-
dicate the position of the circuit breaker via the binary inputs, the test cycle can only
be started when the circuit breaker is closed.
The information regarding the position of the circuit breaker is not automatically de-
rived from the position logic according to Sub-section 6.22.2 (Figure 6-151). For the
circuit breaker test function there are separate binary inputs for the switching status
feedback of the circuit breaker position. These must be taken into consideration when
allocating the binary inputs as mentioned in Section 6.22.2 (Page 294).
The alarms of the device show the respective state of the test sequence.
Table 6-16
Circuit breaker test programs
Seq.
No.
Test cycles
CB
Output alarm
1
1 pole TRIP/CLOSE cycle pole L1
CB 1
CB1-TESTtrip L1 (7325)
2
1pole TRIP/CLOSE cycle pole L2
CB1-TESTtrip L2 (7326)
3
1pole TRIP/CLOSE cycle pole L3
CB1-TESTtrip L3 (7327)
4
3pole TRIP/CLOSE cycle
CB1-TESTtrip123 (7328)
applicable close command
CB1-TEST close (7329)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...