Functions
6-284
7SA6 Manual
C53000-G1176-C156-2
shown. In addition these monitoring alarms are allocated to four different general
alarm categories:
•
Error with a summary alarm
(F.No. 140, i.e. general device failure)
•
Alarm summary event
(F.No. 160, i.e. general supervision alarm)
•
Failure: general current supervision
(F.No. 161)
•
Failure: general voltage supervision
(F.No. 164)
Table 6-13
Summary of the device response to detected failures
Monitoring
Possible causes
Failure response
General alarms
Alarm (function no.)
Output
Auxiliary voltage failure
external (aux. supply)
internal (converter)
device out of service or
alarm
all LEDs dark or
“
Error 5 V
” (144)
D.OK
2
) resets
Measured value
acquisition
internal (converter or
reference voltage)
protection out of serv-
ice, alarm
LED „ERROR”
“
Error A/D-conv.
”
(181)
D.OK
2
) resets
Buffer battery
internal (buffer battery)
alarm
“Fail Battery” (177)
as allocated
Hardware–watchdog
internal (processor fail)
device out of service
LED “ERROR”
D.OK
2
) resets
Software–watchdog
internal (program execu-
tion)
reboot attempt
1
)
LED “ERROR”
D.OK
2
) resets
Working memory
internal (RAM)
reboot attempt
1
)
abortion of the boot
process
device out of service
LED flashes
D.OK
2
) resets
Program memory
internal (EPROM)
reboot attempt
1
)
LED “ERROR”
D.OK
2
) resets
Parameter memory
internal (EEPROM or
RAM)
reboot attempt
1
)
LED “ERROR”
D.OK
2
) resets
Sampling frequency
internal (clock)
reboot attempt
1
)
LED “ERROR”
D.OK
2
) resets
1 A/5 A–setting
jumper settings
1 A/5 A incorrect
alarm
protection out of service
“
Error1A/5Awrong
” (192)
“
Error A/D-conv.
” (181)
LED “ERROR”
D.OK
2
) resets
Calibration data
internal (EEPROM or
RAM)
alarm:
default values used
“
Alarm NO calibr
”
(193)
as allocated
Earth current transformer
sensitive/normal
I/O–module does not cor-
respond to the ordering
code of the device
alarm:
protection out of service
“
Error neutralCT
” (194)
“
Error A/D-conv.
” (181)
LED “ERROR”
D.OK
2
) resets
Modules
module does not corre-
spond to the ordering
code of the device
alarm:
protection out of service
“
Error Board 1...7
”
(183 ... 189)
and if applicable
“
Error A/D-conv.
” (181)
D.OK
2
) resets
Current sum
internal (measured value
acquisition)
alarm
“Failure
Σ
I
” (162)
as allocated
Current symmetry
external (primary plant or
current transformers)
alarm
“
Fail I balance
”(163) as allocated
Broken conductor
external (primary plant or
current transformers)
alarm
“
Fail Conductor
” (195) as allocated
1
) Following three unsuccessful reboot attempts, the device is taken out of service
2
) D.OK = “Device Okay” = Live contact relay
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...