Functions
6-223
7SA6 Manual
C53000-G1176-C156-2
Address
3530
Op.mode with MC
determines whether closing under asynchronous
system conditions is allowed. Set this parameter to
with T-CB close
, if asynchro-
nous closing shall be allowed; the relay will then consider the circuit breaker closing
time before determining the correct instant for the close command. Remember that
closing under asynchronous system conditions is allowed only if the circuit breaker
closing time is set correctly (see above under “Preconditions”)! If you wish to only per-
mit manual closing under synchronous system conditions, set this address to
w/o T-
CB close
.
The permissible magnitude difference of the voltages is set under address
3531
MC
maxVolt.Diff
. Setting is in volts secondary. When operating the device from a per-
sonal computer using DIGSI
®
4, setting may be in secondary or primary values. De-
pending on the connection of the bus-bar voltage (phase–phase or phase–earth) the
phase–phase or the phase–earth voltage is decisive.
The permissible frequency difference between the voltages is set under address
3532
MC maxFreq.Diff
, the permissible phase angle difference under address
3533
MC
maxAngleDiff
.
The release conditions for manual closing are set under addresses
3535A
to
3539
:
3535A
MC SYNCHR
= synchronism check: the bus-bar (Ubus) and the
feeder (Uline) must both be live (
Live Volt.
Thr.
, address
3503
); the conditions for synchro-
nism
MC maxVolt.Diff
(address
3531
),
MC
maxFreq.Diff
(address
3532
), and
MC maxAn-
gleDiff
(address
3533
) are checked before man-
ual closure;
3536
MC Usyn> Uline<
=
dead-line check: the bus-bar (Ubus) must be live
(
Live Volt. Thr.
, refer to address
3503
), the
feeder (Uline) must be dead (
Dead Volt. Thr.
,
refer to address
3502
);
3537
MC Usyn< Uline>
=
dead-bus check: the bus-bar (Ubus) must be dead
(
Dead Volt. Thr.
, refer to address
3502
), the
feeder (Uline) must be live (
Live Volt. Thr.
, re-
fer to address
3503
);
3538
MC Usyn< Uline<
= dead-bus and dead-line check: the bus-bar (Ubus)
and the feeder (Uline) must both be dead (
Dead
Volt. Thr.
, refer to address
3502
);
3539
MC O/RIDE
= manual closing is released without any check.
The five possible release conditions are independent of each other and can be com-
bined.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...