6.15.3 Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
Addr.
Setting Title
Setting Options
Default Setting
Comments
3501
FCT Synchronism
ON
OFF
ON
Synchronism and Voltage Check
function
3502
Dead Volt. Thr.
1..60 V
5 V
Voltage threshold dead line / bus
3503
Live Volt. Thr.
20..125 V
90 V
Voltage threshold live line / bus
3504
Umax
20..140 V
110 V
Maximum permissible voltage
3507
T-SYN. DURATION
0.01..600.00 sec;
∞
1.00 sec
Maximum duration of synchro-
nism-check
3508
T SYNC-STAB
0.00..30.00 sec
0.00 sec
Synchronous condition stability
timer
3510
Op.mode with AR
with consideration of CB clo-
sing time
without consideration of CB
closing time
without considera-
tion of CB closing
time
Operating mode with AR
3511
Max. Volt. Diff
1.0..40.0 V
2.0 V
Maximum voltage difference
3512
Max. Freq. Diff
0.03..2.00 Hz
0.10 Hz
Maximum frequency difference
3513
Max. Angle Diff
2..60
°
10
°
Maximum angle difference
3515A
SYNC-CHECK
YES
NO
YES
Live bus / live line and Sync
before AR
3516
Usync> U-line<
YES
NO
NO
Live bus / dead line check before
AR
3517
Usync< U-line>
YES
NO
NO
Dead bus / live line check before
AR
3518
Usync< U-line<
YES
NO
NO
Dead bus / dead line check
before AR
3519
OVERRIDE
YES
NO
NO
Override of any check before AR
3530
Op.mode with MC
with consideration of CB clo-
sing time
without consideration of CB
closing time
without considera-
tion of CB closing
time
Operating mode with Man.Cl
3531
MC maxVolt.Diff
1.0..40.0 V
2.0 V
Maximum voltage difference
3532
MC maxFreq.Diff
0.03..2.00 Hz
0.10 Hz
Maximum frequency difference
3533
MC maxAngleDiff
2..60
°
10
°
Maximum angle difference
3535A
MC SYNCHR
YES
NO
YES
Live bus / live line and Sync
before MC
3536
MC Usyn> Uline<
YES
NO
NO
Live bus / dead line check before
Man.Cl
3537
MC Usyn< Uline>
YES
NO
NO
Dead bus / live line check before
Man.Cl
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...