Appendix
A-72
7SA6 Manual
C53000-G1176-C156-2
•
the input indication “>CB wait” is set to OPEN and
•
the input indication “>Door open” is set to OPEN.
The disconnector can only be closed, if:
•
the circuit breaker is set to OPEN and
•
the earth switch is set to OPEN and
•
the disconnector is set to OPEN or CLOS and
•
the input indication “>Door open” is set to OPEN.
The disconnector can only be closed, if:
•
the circuit breaker is set to CLOS and
•
the disconnector is set to OPEN or CLOS and
•
the earth switch is set to OPEN or CLOS and
•
the input indication “>Door open” is set to OPEN.
The earth switch can only be closed, if:
•
the circuit breaker is set to OPEN and
•
the disconnector is set to OPEN and
•
the earth switch is set to OPEN or CLOS and
•
the input indication “>Door open” is set to OPEN.
If requirements above-mentioned are not fulfilled, the actions of the switch commands
will be blocked with error messages by DIGSI
®
4.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...