Installation and Commissioning
8-53
7SA6 Manual
C53000-G1176-C156-2
8.3.5
Checking the Communication Topology
General
The communication topology can either be checked from the PC using DIGSI® 4.
You can either connect the PC to the device locally using the operator interface at the
front, or the service interface at the back of the PC (Figure 8-27). Or you can log into
the device using a modem via the service interface (example in Figure 8-28).
I
Figure 8-27 PC interfacing directly to the device - example
Figure 8-28 PC interfacing via modem - example
Checking a
Connection using
Direct Link
For two devices linked with fibre optical cables (as in Figure 8-16 or 8-17), this con-
nection is checked as follows. If two or more device are linked or, if two devices have
been (double-) linked with a ring topology, first check only one link.
o
Both devices at the link ends have to be switched on.
o
Check in the Event Log (see also Subsubsection 7.1.1.2) or spontaneous annuncia-
tions (see Subsubsection 7.1.1.7) for the following:
G
If the message "
PI1 with
" (protection data interface connected with FNo. 3243)
is provided with the device index of the other device, a link has been established
and one device has recognized the other.
o
In the event of a communication link error the message "
PI1 Data fault
" (FNo.
3229) will be displayed. In this case, check the fibre optical cable link again.
G
Have the devices been linked correctly and no cables been mixed up?
G
Are the cables free from mechanical damage, intact and the connectors locked?
G
Otherwise repeat check.
Proceed with "Consistency of Topology and Parameter Setting".
:
7SA6
7SA6
:
7SA6
7SA6
Mo
de
m
Mo
de
m
Mo
de
m
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...