Technical Data
10-36
7SA6 Manual
C53000-G1176-C156
10.15 Voltage Protection (optional)
Overvoltage
Phase–Earth
Overvoltage
U
Ph
>>
1.0 V to 170.0 V;
∞
(steps 0.1 V)
Time delay
T
UPh>>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Overvoltage
U
Ph
>
1.0 V to 170.0 V;
∞
(steps 0.1 V)
Time delay
T
UPh>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
0.50 to 0.98
(steps 0.01)
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Overvoltage
Phase–Phase
Overvoltage
U
PhPh
>>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
UPhPh>>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Overvoltage
U
PhPh
>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
UPhPh>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
0.50 to 0.98
(steps 0.01)
Pick-up time
ca. 30 ms
Drop-off time
ca. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Overvoltage
Positive Sequence
System U
1
Overvoltage
U
1
>>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
U1>>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Overvoltage
U
1
>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
U1>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
0.50 to 0.98
(steps 0.01)
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Overvoltage
Negative Sequence
System U
2
Overvoltage
U
2
>>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
U2>>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Overvoltage
U
2
>
2.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
U2>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
0.50 to 0.98
(steps 0.01)
Pick-up time
approx. 30 ms
Drop-off time
approx. 30 ms
Tolerances
voltages
3 % of set value or 1 V
times
1 % of set value or 10 ms
Overvoltage Zero
Sequence System
3U
0
or any Single-
Phase Voltage U
X
Overvoltage
3U
0
>>
1.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
3U0>>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Overvoltage
3U
0
>
1.0 V to 220.0 V;
∞
(steps 0.1 V)
Time delay
T
3U0>
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Drop-off to pick-up ratio
0.50 to 0.98
(steps 0.01)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...