Functions
6-179
7SA6 Manual
C53000-G1176-C156-2
6.12.2 Applying the Function Parameter Settings
A prerequisite for the operation of the switch-on-to-fault protection is that in address
124
SOTF Overcurr.
=
Enabled
was set during the configuration of the device
scope of functions (Section 5.1). It is furthermore possible to switch the function, in ad-
dress
2401
,
SOTF Overcurr.
ON
or
OFF
.
The magnitude of the current which causes pick-up of the switch on to fault function is
set as
I>>>
in address
2404
. The setting value should be selected large enough to
ensure that the protection under no circumstances picks up due to an overload condi-
tion or due to a current increase resulting from e.g. an automatic reclosure dead time
on a parallel feeder. It is recommended to set at least 2.5 times the rated current of
the feeder.
6.12.3 Settings
Note:
The indicated secondary current values for setting ranges and default settings
refer to I
N
= 1 A. For the nominal current 5 A the current values are to be multiplied
by 5.
6.12.4 Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
2401
FCT SOTF-O/C
ON
OFF
ON
Inst. High Speed SOTF-O/C is
2404
I>>>
1.00..25.00 A
2.50 A
I>>> Pickup
F.No.
Alarm
Comments
4253
>BLOCK SOTF-O/C
>BLOCK Instantaneous SOTF Overcurrent
4271
SOTF-O/C OFF
SOTF-O/C is switched OFF
4272
SOTF-O/C BLOCK
SOTF-O/C is BLOCKED
4273
SOTF-O/C ACTIVE
SOTF-O/C is ACTIVE
4281
SOTF-O/C PICKUP
SOTF-O/C PICKED UP
4282
SOF O/CpickupL1
SOTF-O/C Pickup L1
4283
SOF O/CpickupL2
SOTF-O/C Pickup L2
4284
SOF O/CpickupL3
SOTF-O/C Pickup L3
4295
SOF O/CtripL123
SOTF-O/C TRIP command L123
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...