Functions
6-82
7SA6 Manual
C53000-G1176-C156-2
number identifies the devices in the communication system since the exchange of
information between several Distance Protection systems (thus also for several
protective relay) can be executed via the same communication system.
Please make sure that the possible communications links and the existing interfaces
are in accordance with each other. If all devices are not equipped with two protection
data interfaces, those with only one protection data interface must be located at the
ends of the communication chain. In Figure 6-46 these are the devices with index 1
and 3. In this situation, a ring topology is possible, if all devices of a Distance
Protection system provide two protection data interfaces.
If you work with different physical interfaces and communications links, please make
sure that every protection data interface corresponds to the projected communication
link.
Figure 6-47
Distance Protection topology for 2 ends with 2 devices - example
For a protected object with two ends (e.g. a line) the addresses
4701
ID OF RELAY 1
and
4702
ID OF RELAY 2
are set, e.g. for device 1 the
device-ID
16
and for device 2 the device-ID
17
(Figure 6-47, compare also with Figure
6-44 and 6-45). The indices of the devices and the device-IDs do not have to match,
as mentioned above.
For a protected object with more than two ends (and corresponding devices), further
ends are allocated to their device IDs with the parameter addresses
4703
ID OF
RELAY 3
. A maximum of 3 line ends is possible with 3 devices. Figure 6-48 gives an
example with 3 relays (compare also Figure 6-45 and 6-46) . During the configuration
of the protection functions (Section 5.1) the number of devices required for the
relevant case of application was set in address
147
NUMBER OF RELAY
. Device IDs
can be entered for as many devices as were configured under that address after that
no further IDs are offered during configuration.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...